Application | field installation |
---|
Operating voltage [V] | 26.5...31.6 DC; ("supply class 2" to cULus) |
---|---|
Max. current consumption from AS-i [mA] | 30 |
Max. current load total [A] | 4 |
Integrated watchdog | yes |
Number of inputs and outputs | Number of digital inputs: 4; Number of digital outputs: 4 |
---|
Number of digital inputs | 4; (bidirectional) |
---|---|
Input circuit of digital inputs | PNP |
Sensor supply of the inputs | to PELV |
Power supply [V] | 20...30; (operating voltage "supply class 2" according to cULus) |
Max. total current rating of inputs [mA] | 200 |
Input current High [mA] | 6...10 |
Input current Low [mA] | 0...2 |
Switching level high [V] | > 11 |
Digital inputs protected against short circuits | yes |
Electrical design | AS-i |
---|---|
Number of digital outputs | 4 |
Circuit | PNP |
Voltage range DC [V] | 20...30; (to PELV; via flat cable; operating voltage "supply class 2" according to cULus) |
Max. current load per output [mA] | 2000 |
Short-circuit proof | yes |
Electrically separated | yes |
Ambient temperature [°C] | -25...70 |
---|---|
Protection | IP 67 |
EMC |
|
---|
AS-i version | 2.1 | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
AS-i addressing | IR addressing possible | ||||||||||
Extended addressing mode | no | ||||||||||
AS-i profile | S-7.0.E | ||||||||||
AS-i I/O configuration [hex] | 7 | ||||||||||
AS-i ID code [hex] | 0.E | ||||||||||
Assignment of the data bits |
|
Type of mounting | AS-i flat cables directly connectable |
---|---|
Dimensions [mm] | 60 x 152 x 24 |
Materials | PUR |
Display |
|
---|
Accessories (optional) |
|
---|
Pack quantity | 1 pcs. |
---|
Connector: M12; coding: A |