As a rule, we recommend that you mount the sensors radially to the shaft axis to capture the greatest possible movement and be as close as possible mechanically to the effective area. In case of fixed bearings with high axial force absorption or axial bearings, the recommended measuring direction is axial to the shaft.
The orange dots in the illustrations indicate the approximate sensor position for smaller machines.
If two measurement positions are more than 80cm apart, we recommend that you install additional sensors as illustrated by the grey dots.
Note:
The sensor can monitor all characteristic values simultaneously and provide a switching signal for two selected characteristic values.
Sensor position | Alarms | Root issue | ||
---|---|---|---|---|
Primary sensor | Horizontal driven end |
a-Peak v-RMS a-RMS Temp |
Impact Loose footing Friction (bearing) Overheating |
|
Optional sensor | Vertical non-driven end |
Sensor position | Alarms | Root issue | ||
---|---|---|---|---|
Primary sensor | Horizontal driven end |
a-Peak v-RMS a-RMS Temp |
Impact Loose footing Friction (bearing) Overheating |
|
Optional sensor | Vertical non-driven end |
Sensor position | Alarms | Root issue | ||
---|---|---|---|---|
Primary sensor | Horizontal driven end of motor |
a-Peak v-RMS a-RMS Temp |
Impact Loose footing Friction (bearing) Overheating |
|
Optional sensor | Vertical non-driven end of motor | |||
Primary sensor | Horizontal driven end of fan | |||
Optional sensor | Vertical non-driven end of fan |
Sensor position | Alarms | Root issue | ||
---|---|---|---|---|
Primary sensor | Horizontal driven end of motor |
a-Peak v-RMS a-RMS Temp |
Impact Loose footing Friction (bearing) Overheating |
|
Optional sensor | Vertical non-driven end of motor | |||
Primary sensor | Horizontal driven end of pump | |||
Optional sensor | Vertical non-driven end of pump |
Sensor position | Alarms | Root issue | ||
---|---|---|---|---|
Primary sensor | Horizontal driven end |
a-Peak v-RMS a-RMS Temp |
Impact Loose footing Friction (bearing) Overheating |
|
Optional sensor | Vertical non-driven end |
What is measured? Peak value of the vibration acceleration.
What is detected? Especially shock-like, high-frequency vibrations.
For example influenced by:
What is measured? Effective value of the vibration acceleration.
What is detected? Mechanical friction.
For example influenced by:
What is measured? Effective value of the vibration velocity.
What is detected? The energy the machine is subjected to. An increase can be triggered by low-frequency fault conditions.
For example influenced by:
What is measured? Increased friction or electrical problems resulting in a temperature rise.
For example influenced by:
What is measured? Ratio of a-Peak compared to a-RMS.
What is detected? In combination with a second value (e.g. a-Peak) useful for the evaluation of bearing damage
Influenced by: