Output function | normally open / normally closed; (selectable) |
---|---|
Sensing range [mm] | 20 |
Housing | cylindrical |
Dimensions [mm] | Ø 34 / L = 98 |
Operating voltage [V] | 8...30 DC |
---|---|
Reverse polarity protection | no |
Output function | normally open / normally closed; (selectable) |
---|---|
Max. voltage drop switching output DC [V] | 5.5 |
Minimum load current [mA] | 5 |
Max. leakage current [mA] | 1.4 |
Permanent current rating of switching output DC [mA] | 200 |
Switching frequency DC [Hz] | 40 |
Short-circuit protection | no |
Overload protection | no |
Sensing range [mm] | 20 |
---|---|
Real sensing range Sr [mm] | 20 ± 10 % |
Operating distance [mm] | 0...16.2 |
Correction factor | steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminium: 0.4 / copper: 0.3 |
---|---|
Hysteresis [% of Sr] | 1...15 |
Switch point drift [% of Sr] | -10...10 |
Ambient temperature [°C] | -25...80 |
---|---|
Protection | IP 65 |
EMC |
|
---|
Housing | cylindrical |
---|---|
Mounting | non-flush mountable |
Dimensions [mm] | Ø 34 / L = 98 |
Materials | PBT; end cap: PC |
Display |
|
---|
Items supplied |
|
---|
Pack quantity | 1 pcs. |
---|
Connection | terminals: ...2.5 mm² |
---|