You probably do not come from: Hong Kong SAR China. If necessary, change to: United States
  1. Products
  2. Safety technology
  3. Safety over IO-Link
  4. Safe input/output modules
  5. AL200S

PROFIsafe IO-Link module

AL200S

PROFIsafe IOL Device 8P IP67

PROFIsafe IO-Link module

AL200S

PROFIsafe IOL Device 8P IP67

  • Safe I/O module for PROFIsafe with safe inputs and outputs
  • Connection of safe mechanical contacts and OSSD sensors possible
  • PROFIsafe telegrams tunnelled via IO-Link
  • Separate 24 V power supply of the outputs via standardised M12 L coding for high current rating
  • Safety product in combination with IO-Link
  • ce
  • ukca
  • profisafe
  • cul
  • iolink
Application
Design only for operation with IO-Link masters AL140x, AL1304 to AL1307 and Siemens PLCs S7-1200 and S7-1500 (except software controller and open controller)
Application I/O modules for field applications
Electrical data
Operating voltage [V] 19.2...30.2 DC; (US ; to SELV/PELV)
Current consumption [mA] 67; (US)
Protection class III
Additional voltage supply [V] 19.2...30.2 DC; (UA)
Max. current consumption from additional supply [mA] 34; (UA)
Actuator supply UA
Max. current load total [A] 6
Current rating per port [A] 2
Inputs / outputs
Total number of inputs and outputs 12
Inputs
Total number of inputs 8
Switching level high [V] 11...30
Switching level low [V] -30...5
Digital inputs protected against short circuits yes
Outputs
Total number of outputs 4
Short-circuit proof yes
Interfaces
Communication interface IO-Link
Supported DeviceIDs
Type of operation DeviceID
default 1312
IO-Link Device
Transmission type COM3 (230,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
SIO mode no
Operating conditions
Ambient temperature [°C] -25...60
Storage temperature [°C] -40...85
Max. relative air humidity [%] 75
Protection IP 65; IP 67
Tests / approvals
EMC
EN 61000-6-2
EN 61000-4-2 ESD 6 kV CD / 8 kV AD
EN 61000-4-3 HF radiated 10 V/m
EN 61000-4-4 Burst 2 kV
EN 61000-4-5 Surge
EN 61000-4-6 HF conducted
Shock resistance
DIN EN 60068-2-27
Vibration resistance
DIN EN 60068-2-64 2009-04
DIN EN 60068-2-6 2008-10
Safety classification
Mission time TM [h] 175200
Mission time TM (additional indication)
20 years
Single channel
Complies with the requirements
ISO 13849-1 PL d
IEC 61508 SIL 2
IEC 62061 SIL 2
PFH [1/h] 1E-08
PFD [1/h] 1E-04
Dual channel
Complies with the requirements
ISO 13849-1 PL e
IEC 61508 SIL 3
IEC 62061 SIL 3
PFH [1/h] 1E-09
PFD [1/h] 1E-05
Mechanical data
Weight [g] 408.3
Materials housing: PA; socket: brass nickel-plated
Remarks
Remarks
Safety classification depends on parameterisation and wiring (see operating instructions).
Pack quantity 1 pcs.
Electrical connection - Address Plug
X41 Connector: M12; coding: A
Electrical connection - IO-Link
X21 Connector: M12; coding: A
Electrical connection - Power IN
X31 Connector: M12; coding: L
Electrical connection - Safety Inputs
X01...X04 Connector: M12; coding: A
Electrical connection - Safety Outputs
X05...X08 Connector: M12; coding: A