You probably do not come from: Hong Kong SAR China. If necessary, change to: United States
  1. Products
  2. Industrial communication
  3. AS-Interface I/O modules
  4. Field modules with quick mounting technology ClassicLine
  5. AC5205

AS-Interface ClassicLine module with quick mounting technology

AC5205

ClassicLine 4DI IP67

AS-Interface ClassicLine module with quick mounting technology

AC5205

ClassicLine 4DI IP67

  • Easy toolless installation and wiring thanks to quick mounting technology
  • Three freely selectable directions of the flat cable
  • Clearly visible powerful LEDs for displaying operation, switching status and error
  • High protection rating for the requirements of harsh industrial environments
  • Robust M12 connectors for connecting sensors and actuators
  • ce
  • ukca
  • asib
  • cul
Application
Application field installation
Electrical data
Operating voltage [V] 26.5...31.6 DC; ("supply class 2" to cULus)
Max. current consumption from AS-i [mA] 250
Inputs / outputs
Number of inputs and outputs Number of digital inputs: 4
Inputs
Number of digital inputs 4
Input circuit of digital inputs PNP
Sensor supply of the inputs AS-i
Power supply [V] 18...30; (via flat cable)
Max. total current rating of inputs [mA] 200
Input current High [mA] 6...10
Input current Low [mA] 0...2
Switching level high [V] > 11
Digital inputs protected against short circuits yes
Operating conditions
Ambient temperature [°C] -25...70
Protection IP 67
Tests / approvals
EMC
EN 50295
IEC 61000-6-2
MTTF [years] 404
AS-i classification
AS-i version 2.11; 3.0
AS-i addressing addressing socket
Extended addressing mode no
AS-i master profile M2; M3; M4
AS-i profile S-0.0.E
AS-i I/O configuration [hex] 0
AS-i ID code [hex] 0.E
Assignment of the data bits
data bit D0 D1 D2 D3
input 1 2 3 4
socket I-1 I-2 I-3 I-4
pin 2+4 2+4 2+4 2+4
Mechanical data
Weight [g] 155.1
Type of mounting AS-i flat cables directly connectable
Materials PA; piercing contacts: CuSn6 nickel-plated and tin-plated
Displays / operating elements
Display
operation LED, green
errors LED, red
function LED, yellow
Electrical connection
Module connection Flat cables
Accessories
Items supplied
lower part
Accessories (optional)
Addressing cable:, E70213
Protective cap: M12, E73004
Remarks
Remarks
Only use addressing cable E70213.
Do not use addressing cables from other manufacturers.
Short circuits or irreparable deformation of the addressing socket cannot be excluded.
Do not connect any of the following points to an external potential:
I-, I+, I1, I2, I3, I4
The connections are electrically connected with the AS-i cable.
Pack quantity 1 pcs.
Electrical connection
quick mounting technology for AS-i flat cable: ; three orientations possible
Connector: M12; coding: A