  5. AC514A

AS-Interface ClassicLine module with quick mounting technology

AC514A

ClassicL 2DO-Y 2DI-Y II 3D

AS-Interface ClassicLine module with quick mounting technology

AC514A

ClassicL 2DO-Y 2DI-Y II 3D

  • Easy toolless installation and wiring thanks to quick mounting technology
  • Three freely selectable directions of the flat cable
  • Clearly visible powerful LEDs for displaying operation, status and function
  • For applications in hazardous areas
  • Robust M12 connectors for connecting sensors and actuators
  • ce
  • ukca
  • ex
  • asib
Application
Application AS-i ATEX module
Electrical data
Operating voltage [V] 26.5...31.6 DC
Max. current consumption from AS-i [mA] 150
Max. current load total [A] 2
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital inputs: 2; Number of digital outputs: 2
Inputs
Number of digital inputs 2
Input circuit of digital inputs PNP
Sensor supply of the inputs AS-i
Power supply [V] 18...30; (via flat cable)
Max. total current rating of inputs [mA] 100
Input current High [mA] 6...10
Input current Low [mA] 0...2
Switching level high [V] > 11
Digital inputs protected against short circuits yes
Outputs
Number of digital outputs 2
Circuit PNP
Voltage range DC [V] 15...30; (to PELV; via flat cable)
Max. current load per output [mA] 1000; (utilisation category DC-13 (control of electromagnets): 20 W (IEC 60947-5-1))
Short-circuit proof yes
Electrically separated yes
Operating conditions
Ambient temperature [°C] -10...50
Protection IP 50
Tests / approvals
ATEX marking II 3D Ex tc IIIB T80°C Dc X IP50
EMC
EN 50295
IEC 61000-6-2
MTTF [years] 192
AS-i classification
AS-i version 2.11; 3.0
AS-i addressing addressing socket
Extended addressing mode yes
AS-i master profile M2; M3; M4
AS-i profile S-B.A.E
AS-i I/O configuration [hex] B
AS-i ID code [hex] A.E
AS-i certificate pending yes
Assignment of the data bits
data bit D0 D1 D2 D3
input - - 3 4
socket - - I-3/4 I-3/4 I-4
pin - - 4 2 4
Output 1 2 - -
socket O-1/2 O-1/2 / O-2 - -
pin 4 2 4 - -
Mechanical data
Weight [g] 239.5
Type of mounting AS-i flat cables directly connectable
Materials PA; piercing contacts: CuSn6 nickel-plated and tin-plated
Displays / operating elements
Display
operation LED, green
errors LED, red
function LED, yellow
Electrical connection
Module connection Flat cables
Accessories
Items supplied
lower part
Accessories (optional)
Protective cap: M12, E73004
Impact protection housing:, E7000A
Remarks
Remarks
Mechanical protection has to be implemented.
Otherwise the unit must be installed together with the impact protection housing (E7000A).
Do not connect any of the following points to an external potential:
I-, I+, I-3/4, I-4
The connections are electrically connected with the AS-i cable.
Inputs and outputs must be electrically isolated.
Pack quantity 1 pcs.
Electrical connection
Connection quick mounting technology for AS-i flat cable: ; three orientations possible
Electrical connection - Inputs
Connection Connector: M12
Electrical connection - Outputs
Connection Connector: M12