Electrical data
Operating voltage [V] 26.5...31.6 DC
Max. current consumption from AS-i [mA] 240
Inputs / outputs
Number of inputs and outputs Number of digital inputs: 4
Inputs
Number of digital inputs 4
Input circuit of digital inputs PNP
Sensor supply of the inputs AS-i
Power supply [V] 20...30
Max. total current rating of inputs [mA] 200
Input current High [mA] 6...10
Input current Low [mA] 0...2
Switching level high [V] > 11
Digital inputs protected against short circuits yes
Outputs
Electrical design AS-i
Operating conditions
Ambient temperature [°C] 0...40
Protection IP 67
Tests / approvals
ATEX marking II 3G EEx nA II T6 X
II 3D T60 °C IP 67 X
EMC
EN 50295
AS-i classification
AS-i version 2.1
AS-i addressing IR addressing possible
Extended addressing mode no
AS-i profile S-0.0.E
AS-i I/O configuration [hex] 0
AS-i ID code [hex] 0.E
AS-i certificate pending yes
Assignment of the data bits
data bit D0 D1 D2 D3
socket I-1 I-2 I-3 I-4
pin 2+4 2+4 2+4 2+4
Mechanical data
Type of mounting AS-i interface to FC lower parts
Materials PBT
Displays / operating elements
Display
operation LED, green
errors LED, red
function LED, yellow
Accessories
Items supplied
Module lower part, AC5000
Remarks
Remarks
Do not connect any of the following points to an external potential:
I-, I+, I1, I2, I3, I4
The connections are electrically connected with the AS-i cable.
Use M12 connectors with hexagon nuts, tightening torque 0.8 Nm.
Pack quantity 1 pcs.
Electrical connection
Connector: M12; coding: A