Compressed air meter

SD1540

SDD11DGXFRKG/US-100

Compressed air meter

SD1540

SDD11DGXFRKG/US-100

  • Precise measurement of flow, consumption, pressure and medium temperature
  • High accuracy, repeatability and measurement dynamics
  • For detecting compressed air in industrial use
  • With switching output, analogue output and pulse output
  • Adjustable to inside pipe diameters
  • Convenient operation via buttons or parameter setting via IO-Link
  • ce
  • ukca
  • iolink
  • cul
  • crn
Product characteristics
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Measuring range
0.6...143.9 m/s 0.3...26260 m³/h 0.005...437.6 m³/min
Process connection threaded connection G 1 internal thread
Application
Application for industrial applications
Installation Adjustable to inside pipe diameters; ( 14...254 mm)
Media compressed air
Medium temperature [°C] -10...60
Min. bursting pressure [bar] 64
Min. bursting pressure [MPa] 6.4
Pressure rating [bar] 16
Pressure rating [MPa] 1.6
MAWP (for applications according to CRN) [bar] 10
Electrical data
Operating voltage [V] 18...30 DC; (to SELV/PELV)
Current consumption [mA] < 80
Protection class III
Reverse polarity protection yes
Power-on delay time [s] 1
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Inputs
Inputs counter reset
Outputs
Output signal switching signal; analogue signal; pulse signal; IO-Link; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V] 2.5
Permanent current rating of switching output DC [mA] 150; (per output)
Number of analogue outputs 1
Analogue current output [mA] 4...20; (scalable)
Max. load [Ω] 500
Pulse output consumed quantity meter
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
Measuring/setting range
Measuring range
0.6...143.9 m/s 0.3...26260 m³/h 0.005...437.6 m³/min
Display range
0...172.7 m/s 0...31520 m³/h 0...525.2 m³/min
Resolution
0.1 m/s 0.05 m³/h 0.01 m³/min
Set point SP
1.4...143.9 m/s 0.8...26260 m³/h 0.013...437.6 m³/min
Reset point rP
0.7...143.2 m/s 0.4...26140 m³/h 0.007...435.6 m³/min
Analogue start point ASP
0...115.1 m/s 0...21000 m³/h 0...350 m³/min
Analogue end point AEP
28.8...143.9 m/s 422...26260 m³/h 7.04...437.6 m³/min
Low flow cut-off LFC
0.2...1.4 m/s 0.1...260 m³/h 0.002...4.4 m³/min
In steps of
0.1 m/s 0.01 m³/h 0.001 m³/min
Pressure monitoring
Measuring range [bar] -1...16
Display range [bar] -1...20
Resolution [bar] 0.05
Set point SP [bar] -0.92...16
Reset point rP [bar] -1...15.92
Analogue start point [bar] -1...12.8
Analogue end point [bar] 2.2...16
In steps of [bar] 0.01
Volumetric flow quantity monitoring
Measuring range
0...1000000000 m³ 0...35314666721 scf
Display range
0...1000000000 m³ 0...35314666721 scf
Set point SP
0.01...100000000 m³ 0.35...3531466672.1 scf
Pulse value
0.01...100000000 m³ 0.35...3531466672.1 scf
In steps of
0.001 m³ 0.05 scf
Pulse length [s] 0.001...2
Temperature monitoring
Measuring range
-10...60 °C 14...140 °F
Display range
-24...74 °C -11.2...165.2 °F
Resolution
0.2 °C 0.5 °F
Set point SP
-9.7...60 °C 14.6...140 °F
Reset point rP
-10...59.7 °C 14...139.4 °F
Analogue start point
-10...46 °C 14...114.8 °F
Analogue end point
4...60 °C 39.2...140 °F
In steps of
0.1 °C 0.1 °F
Accuracy / deviations
Temperature coefficient [1/K] ± 0,07 % MW
Accuracy (in the measuring range) ± (6 % MW + 0,6 % MEW); (reference conditions: diA = 73 mm; inlet pipe length >= 3 m; outlet pipe length >= 0,5 m; reference temperature: 20...25 °C; standard volume flow: 50...850 Nm³/h)
Repeatability ± 1,5 % MW
Pressure monitoring
Repeatability [% of the final value] ± 0,2
Characteristics deviation [% of the final value] < ± 0,5; (BFSL = Best Fit Straight Line)
Greatest TEMPCO of the span [% MEW / 10 K] ± 0,3
Greatest TEMPCO of the zero point [% MEW / 10 K] ± 0,1
Temperature monitoring
Accuracy [K] ± 0,5; (medium flow in the limit area of the flow measurement range)
Response times
Response time [s] 0.1; (dAP = 0)
Damping process value dAP [s] 0...5
Pressure monitoring
Response time [s] 0.05
Temperature monitoring
Dynamic response T05 / T09 [s] T09 = 0,5
Software / programming
Parameter setting options hysteresis / window; normally open / normally closed; current/pulse output; display can be rotated and switched off; Display unit; totaliser
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9 CDV
Profiles Digital Measuring Sensor (0x800A), Identification and Diagnosis (0x4000)
SIO mode yes
Required master port type A
Process data analogue 8
Process data binary 2
Min. process cycle time [ms] 7.2
Supported DeviceIDs
Type of operation DeviceID
default 872
Operating conditions
Ambient temperature [°C] 0...60
Storage temperature [°C] -20...85
Max. relative air humidity [%] 90
Protection IP 65; IP 67
Tests / approvals
EMC
DIN EN 60947-5-9
CPA approval
model number -
accuracy class -
maximum allowable error ± 7 % FS
Q (min) 0,3 m³/h
Q (t) -
Q (max) 26260 m³/h
Vibration resistance
DIN EN 68000-2-6 5 g (10...2000 Hz)
MTTF [years] 180
UL approval
UL Approval no. I013
File number UL E174189
Mechanical data
Weight [g] 408.3
Materials PBT+PC-GF30; PPS GF40; stainless steel (1.4301 / 304); stainless steel (1.4305 / 303); stainless steel (1.4404 / 316L); FKM
Materials (wetted parts) stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); FKM; ceramics glass passivated; PPS GF40; Al2O3 (ceramics); acrylate
Process connection threaded connection G 1 internal thread
Displays / operating elements
Display
colour display 1,44", 128 x 128 pixels
2 x LED, yellow
Remarks
Remarks
MW = measured value
MEW = Final value of the measuring range
D = inside pipe diameter
Measuring, display and setting ranges refer to the standard volume flow according to DIN ISO 2533.
For information about installation and operation please see the operating instructions.
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12; coding: A