Electrical design | NAMUR |
---|---|
Output function | 2 x normally closed |
Sensing range [mm] | 4 |
Housing | rectangular |
Dimensions [mm] | 40 x 26 x 26 |
Connection at circuit amplifier | yes |
---|---|
Switching amplifiers | connection to certified intrinsically safe circuits with the max. values: U = 15 V / I = 50 mA / P = 120 mW |
Nominal voltage DC [V] | 8.2; (1kΩ) |
Supply voltage DC [V] | 7.5...15 |
Current consumption [mA] | < 1; (disabled; conductive: > 2,1) |
Electrical design | NAMUR |
---|---|
Output function | 2 x normally closed |
Switching frequency DC [Hz] | 1800 |
Sensing range [mm] | 4 |
---|---|
Real sensing range Sr [mm] | 4 ± 10 % |
Correction factor | steel: 1 / stainless steel: 0.7 / brass: 0.5 / aluminum: 0.4 / copper: 0.3 |
---|---|
Hysteresis [% of Sr] | 1...15 |
Switch-point drift [% of Sr] | -10...10 |
Ambient temperature [°C] | -20...70 |
---|---|
Protection | IP 67 |
Approval | DMT 02 ATEX E 028 | ||
---|---|---|---|
ATEX marking | II 1G EEx ia IIB T6 | ||
II 2G EEx ia IIC T6 | |||
EMC |
|
||
Shock/vibration resistance | 30 g (11 ms) / 10-55 Hz (1 mm) |
Max. internal capacitance [nF] | 140; (per intrinsically safe electric circuit) |
---|---|
Max. internal inductance [µH] | 135; (per intrinsically safe electric circuit) |
Housing | rectangular |
---|---|
Mounting | non-flush mountable |
Dimensions [mm] | 40 x 26 x 26 |
Material | PBT |
Display |
|
---|
Pack quantity | 1 pcs. |
---|
Connection | Cable: 6 m, silicone; 4 x 0.34 mm² |
---|