Service Center 800-441-8246
  1. Products
  2. Sensors
  3. Valve sensors
  4. Sensors for quarter-turn actuators
  5. N95001

Inductive NAMUR dual sensor for valve actuators

N95001

IND2004DN/T1/1D/2G

Inductive NAMUR dual sensor for valve actuators

N95001

IND2004DN/T1/1D/2G

  • For monitoring valve positions
  • For reliable position feedback on valve actuators
  • For applications in hazardous areas
  • For connection to intrinsically safe circuits
  • Direct triggering of the solenoid valve from the sensor
  • ce
  • ccc
  • ukca
  • ex
  • iec
Product characteristics
Electrical design NAMUR
Output function 2 x normally closed
Sensing range [mm] 4
Housing rectangular
Dimensions [mm] 40 x 26 x 60
Application
Application For mechanical interfaces to ISO 5211 (VDI/VDE)
Electrical data
Connection at circuit amplifier yes
Switching amplifiers connection to certified intrinsically safe circuits with the max. values: U = 15 V / I = 50 mA / P = 120 mW
Nominal voltage DC [V] 8.2; (1kΩ)
Current consumption [mA] < 1; (disabled; conductive: > 2,2)
Protection class III
Outputs
Electrical design NAMUR
Output function 2 x normally closed
Switching frequency DC [Hz] 250
Monitoring range
Sensing range [mm] 4
Real sensing range Sr [mm] 4 ± 10 %
Accuracy / deviations
Correction factor steel: 1 / stainless steel: 0.7 / brass: 0.5 / aluminum: 0.4 / copper: 0.3
Hysteresis [% of Sr] 1...15
Switch-point drift [% of Sr] -10...10
Operating conditions
Ambient temperature [°C] -20...70
Protection IP 67
Tests / approvals
Approval BVS 03 ATEX E 131 X; BVS 04 ATEX E 153 X; IECEX BVS 06.0003X
ATEX marking II 2G Ex ia IIC T6 Gb Ta -20...70°C
II 2G Ex ia IIC T5 Gb Ta -20...80°C
II 1D Ex ia IIIB T20090°C Da Ta: -20...70°C
II 1D Ex ia IIIB T200100° C Da Ta: -20...80°C
EMC
EN 60947-5-6
Shock/vibration resistance 30 g (11 ms) / 10-55 Hz (1 mm)
MTTF [years] 1232
Safety classification
Max. internal capacitance [nF] 150; (per intrinsically safe electric circuit)
Max. internal inductance [µH] 150; (per intrinsically safe electric circuit)
Mechanical data
Weight [g] 175
Housing rectangular
Mounting non-flush mountable
Dimensions [mm] 40 x 26 x 60
Material housing: PBT; cover: PC
Displays / operating elements
Display
Switching status 2 x LED, yellow
Remarks
Remarks
solenoid valve circuit Ex-i:
connection to certified intrinsically safe circuits with the max. values:
U = 28 V DC / P = 2 W
Pack quantity 1 pcs.
Electrical connection - Socket
Connector: 1 x M12; coding: A
Electrical connection - plug
Connection Connector: Rd24; coding: A