Service Center 800-441-8246
  1. Products
  2. Industrial communication
  3. AS-Interface I/O modules
  4. Field I/O with quick mounting technology
  5. AC5210

AS-Interface ClassicLine module with quick mounting technology

AC5210

ClassicLine 8DI-Y IP67

AS-Interface ClassicLine module with quick mounting technology

AC5210

ClassicLine 8DI-Y IP67

  • Easy toolless installation
  • Three selectable directions of the flat cable mounting
  • Clearly visible powerful LEDs for displaying operation, switching status and error
  • High protection rating for the requirements of harsh industrial environments
  • Robust M12 connectors for connecting sensors and actuators
  • ce
  • ukca
  • asi
  • cul
Application
Application field installation
Electrical data
Operating voltage [V] 26.5...31.6 DC; (cULus - Class 2 source required)
Max. current consumption from AS-i [mA] 300
Inputs / outputs
Number of inputs and outputs Number of digital inputs: 8
Inputs
Number of digital inputs 8; (2 x Slave)
Input circuit of digital inputs PNP
Sensor supply of the inputs AS-i
Voltage supply [V] 18...30
Max. total current rating of inputs [mA] 250; (2 x 125)
Input current High [mA] 6...10
Input current low [mA] 0...2
Switching level high [V] > 11
Digital inputs protected against short circuits yes
Operating conditions
Ambient temperature [°C] -25...70
Protection IP 67
Tests / approvals
EMC
EN 50295
IEC 61000-6-2
MTTF [years] 218
AS-i classification
AS-i version 2.11; 3.0
AS-i addressing Addressing socket
Extended addressing mode yes
AS-i master profile M2; M3; M4
AS-i profile S-0.A.E
AS-i I/O configuration [hex] 0
AS-i ID code [hex] A.E
AS-i certificate 89001
Data bits
Data bit D0 D1 D2 D3
Input 1 2 3 4
Socket I-1/2 I-1/2 I-2 I-3/4 I-3/4 I-4
Pin 4 2 4 4 2 4
Mechanical data
Weight [g] 284.5
Type of mounting AS-i flat cable connection
Material PA; Piercing contacts: CuSn6 nickel-plated and tin-plated
Displays / operating elements
Display
Power LED, green
errors LED, red
Function LED, yellow
Electrical connection
Module connection Flat cable
Accessories
Items supplied
lower part
Accessories (optional)
Protective cap: M12, E73004
Remarks
Remarks
Do not connect any of the following points to an external potential:
I-, I+, I1, I2, I3, I4
The connections are electrically connected with the AS-i cable.
Default setting of the ID1 codes: slave 1=1 / slave 2=2
Pack quantity 1 pcs.
Electrical connection
Connection quick mounting technology for AS-i flat cable: ; three selectable directions
Connection Connector: M12