Product characteristics |
Electrical design |
AS-i |
Sensing range [mm] |
15 |
Housing |
rectangular |
Dimensions [mm] |
40 x 40 x 54 |
Electrical data |
Operating voltage [V] |
26.5...31.6 DC |
Current consumption [mA] |
< 35 |
Protection class |
III |
Reverse polarity protection |
yes |
Outputs |
Electrical design |
AS-i |
Switching frequency DC [Hz] |
100 |
Detection zone |
Sensing range [mm] |
15 |
Operating distance [mm] |
0...12.1 |
Accuracy / deviations |
Correction factor |
steel: 1 / stainless steel: 0.7 / brass: 0.5 / aluminium: 0.5 / copper: 0.4 |
Hysteresis [% of Sr] |
1...20 |
Switch point drift [% of Sr] |
-10...10 |
Operating conditions |
Ambient temperature [°C] |
-25...70 |
Protection |
IP 67 |
Tests / approvals |
EMC |
EN 61000-4-2 ESD |
4 kV CD / 8 kV AD |
EN 61000-4-3 HF radiated |
10 V/m |
EN 61000-4-4 Burst |
2 kV |
EN 61000-4-6 HF conducted |
10 V |
EN 55011 |
class B |
|
MTTF [years] |
958 |
AS-i classification |
AS-i version |
3.0 |
Extended addressing mode possible |
yes |
AS-i I/O configuration [hex] |
0 |
AS-i ID code [hex] |
A.E |
AS-i certificate |
71901 |
Assignment of the data bits |
Designation |
switching signal |
unsafe zone |
readiness for operation |
not used |
status = 0 |
target outside the active zone, yellow LED off |
target within the uncertain zone, red LED flashes |
unit faulty or distance to medium < 10 %, red LED flashes |
- |
status = 1 |
target within the active zone, yellow LED on |
target outside the uncertain zone, red LED off |
readiness for operation, red LED off |
default value |
|
Mechanical data |
Weight [g] |
151.5 |
Housing |
rectangular |
Sensing face |
5 positions selectable |
Mounting |
flush mountable |
Dimensions [mm] |
40 x 40 x 54 |
Materials |
PBT; PPE |
Displays / operating elements |
Display |
switching status |
1 x LED, yellow |
function |
1 x LED, red |
|
Remarks |
Pack quantity |
1 pcs. |
Electrical connection - plug |
Connection |
Connector: 1 x M12; Locking: locking, rotatable |