You probably do not come from: Latvia. If necessary, change to: United States
  1. Products
  2. Industrial communication
  3. AS-Interface I/O modules
  4. Field modules with quick mounting technology ClassicLine
  5. AC522A

AS-Interface ClassicLine module with quick mounting technology

AC522A

ClassicLine 2AI C II 3D

AS-Interface ClassicLine module with quick mounting technology

AC522A

ClassicLine 2AI C II 3D

  • Easy toolless installation and wiring thanks to quick mounting technology
  • Three freely selectable directions of the flat cable
  • Clearly visible powerful LEDs for displaying operation, switching status and error
  • For applications in hazardous areas
  • Robust M12 connectors for connecting sensors and actuators
  • ce
  • ukca
  • ex
  • asib
Application
Application AS-i ATEX module
Electrical data
Operating voltage [V] 26.5...31.6 DC
Max. current consumption from AS-i [mA] 250
Reverse polarity protection yes
Inputs / outputs
Number of inputs and outputs Number of analogue inputs: 2
Inputs
Sensor supply of the inputs AS-i
Number of analogue inputs 2; (Anschluss von 2- und 3-Draht-Sensoren)
Analogue input (current) [mA] 4...20
Analogue inputs protected against short circuits yes
Resolution of analogue input 12 bit
Operating conditions
Ambient temperature [°C] -10...50
Protection IP 50
Tests / approvals
ATEX marking II 3D Ex tc IIIB T80°C Dc X IP50
EMC
EN 50295
MTTF [years] 174
AS-i classification
AS-i version 2.11; 3.0
AS-i addressing addressing socket
Extended addressing mode no
AS-i master profile M3; M4
AS-i profile S-7.3.D
AS-i I/O configuration [hex] 7
AS-i ID code [hex] 3.D
AS-i certificate pending yes
Mechanical data
Weight [g] 233
Type of mounting AS-i flat cables directly connectable
Materials PA; piercing contacts: CuSn6 nickel-plated and tin-plated
Displays / operating elements
Display
operation LED, green Voltage AS-i
errors LED, red
function LED, yellow channels AI1, AI2
Electrical connection
Module connection Flat cables
Accessories
Items supplied
lower part
Accessories (optional)
Protective cap: M12, E73004
Impact protection housing:, E7000A
Remarks
Remarks
Mechanical protection has to be implemented.
Otherwise the unit must be installed together with the impact protection housing (E7000A).
When the actuators are supplied from AS-i the load must not exceed a maximum of 200 mA.
There is an electrical connection between the sensor and AS-i.
Pack quantity 1 pcs.
Electrical connection
quick mounting technology for AS-i flat cable: ; three orientations possible
Connector: M12; coding: A