Application |
Application |
Flow monitoring; Wire monitoring |
Electrical data |
Operating voltage tolerance [%] |
-10...10 |
Operating voltage [V] |
< 110 AC |
Power-on delay time [s] |
30 |
Outputs |
Electrical design |
relay |
Contact rating |
4 A, 250 V AC / cos phi > 07 |
Switching function flow monitoring |
relay energised when flow is present |
Switching function wire break monitoring |
relay de-energised in case of wire break |
Software / programming |
Adjustment of the switch point |
potentiometer |
Selection liquids / gases |
slide switch |
Operating conditions |
Ambient temperature [°C] |
-20...60 |
Protection |
IP 40 |
Protection rating terminals |
IP 20 |
Tests / approvals |
Approval |
PTB Ex-94.C.2030X |
Safety classification |
Designation |
in protection rating intrinsic safety |
Voltage [V] |
15,8 |
Current [mA] |
228 |
Power [mW] |
1410 |
[Ex ia] IIC designation |
[EEx ia] IIC |
[Ex ia] IIB designation |
[EEx ia] IIB |
[Ex ib] IIC designation |
[EEx ib] IIC |
[Ex ib] IIB designation |
[EEx ib] IIB |
[Ex ia] IIC inductance |
350µH |
[Ex ia] IIB inductance |
1mH / 2mH |
[Ex ib] IIC inductance |
350µH |
[Ex ib] IIB inductance |
3.1mH |
[Ex ia] IIC capacitance |
57nF |
[Ex ia] IIB capacitance |
493nF / 294nF |
[Ex ib] IIC capacitance |
477nF |
[Ex ib] IIB capacitance |
1.9µF |
Mechanical data |
Housing |
housing for DIN rail mounting |
Dimensions [mm] |
75 x 55 x 110 |
Materials |
plastics |
Displays / operating elements |
Display |
function |
11 x LED |
switching status |
LED, red |
|
Remarks |
Remarks |
Caution The control monitor must be mounted outside the hazardous area. |
|
Pack quantity |
1 pcs. |
Electrical connection |
Connection |
terminals: 16 x ...2.5 mm² |