1. Homepage
  2. Products
  3. Industrial communication
  4. Fieldbus components
  5. IO-Link - Masters for field applications in factory automation
  6. AL1100

IO-Link master with PROFINET interface

AL1100

IO-Link Master SL PN 4P IP67

IO-Link master with PROFINET interface

AL1100

IO-Link Master SL PN 4P IP67

  • Reliable transmission of machine data, process parameters and diagnostic data to the controller
  • For connection of up to four IO-Link devices
  • With integrated PROFINET interface
  • Robust housing for use in harsh industrial environments
{{ifmVariantName}}



  • ce
  • iolink
  • cul
  • profinet
Technical details
Application
Application I/O modules for field applications
Daisy-chain function fieldbus interface
Electrical data
Operating voltage [V] 20...30 DC; (US; to SELV/PELV)
Current consumption [mA] 300...3900; (US)
Protection class III
Sensor supply US
Max. current load total [A] 3.6
Inputs / outputs
Total number of inputs and outputs 8; (configurable)
Number of inputs and outputs Number of digital inputs: 8; Number of digital outputs: 4
Inputs
Number of digital inputs 8; (IO-Link Port Class A: 4 x 2)
Switching level high [V] 11...30
Switching level low [V] 0...5
Digital inputs protected against short circuits yes
Outputs
Number of digital outputs 4; (IO-Link Port Class A: 4 x 1)
Max. current load per output [mA] 300
Short-circuit proof yes
Interfaces
Communication interface Ethernet; IO-Link
Ethernet
Transmission standard 10Base-T; 100Base-TX
Transmission rate 10; 100
Protocol PROFINET
Factory settings
IP address: 0.0.0.0
subnet mask: 0.0.0.0
gateway IP address: 0.0.0.0
MAC address: see type label
IO-Link Master
Transmission type COM1 (4,8 kBaud); COM2 (38,4 kBaud); COM3 (230,4 kBaud)
IO-Link revision 1.1
Number of ports class A 4
Operating conditions
Ambient temperature [°C] -25...60
Storage temperature [°C] -25...85
Max. relative air humidity [%] 90
Protection IP 65; IP 66; IP 67
Degree of soiling 2
Tests / approvals
EMC
EN 61000-6-2
EN 61000-6-4
Shock resistance
DIN EN 60068-2-27
Vibration resistance
DIN EN 60068-2-64 2009-04
DIN EN 60068-2-6 2008-10
MTTF [years] 90
Mechanical data
Weight [g] 262.5
Materials housing: PA; socket: brass nickel-plated
Remarks
Remarks
For further information please see the operating instructions.
Pack quantity 1 pcs.
Electrical connection - Ethernet
IN / OUT X21, X22 Connector: 2 x M12
Electrical connection - Process connection
IO-Link Port Class A X01...X04 Connector: 4 x M12
Electrical connection - voltage supply
X31 Connector: 1 x M12
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — AL1100-01 — 01.03.2019 —

Startup Package - Profinet

AL1100 | AL1101 | AL1102 | AL1103 | AL1200 | AL1201 | AL1202 | AL1203 | AL1300 | AL1301 | AL1302 | AL1303 | AL1400 | AL1401 | AL1402 | AL1403 | AL1900 | ZZ1100

Version 23.0.0 - 12/2020

  • Name
  • Size
  • Type
  • Description

Firmware | Description file

AL1100 | AL1101 | AL1102 | AL1103 | AL1200 | AL1201 | AL1202 | AL1203 | ZZ1100

Version 2.3.23 - 11/2019

  • Name
  • Size
  • Type
  • Description

Configuration Tool

AL1100 | AL1101 | AL1102 | AL1103 | AL1120 | AL1121 | AL1122 | AL1123 |AL1200 | AL1201 | AL1202 | AL1203 | AL1220 | AL1221 | AL1222 | AL1223 | AL1300 | AL1301 | AL1302 | AL1303 |AL1320 | AL1321 | AL1322 | AL1323 | AL1330 | AL1331 | AL1332 | AL1333 | AL1340 | AL1341 | AL1342 | AL1343 | AL1350 | AL1351 | AL1352 | AL1353 | AL1400 | AL1401 | AL1402 | AL1403 | AL1420 | AL1421 | AL1422 | AL1423 | AL1900 | AL1920 | AL1930 | AL1940 | AL1950 | ZZ1100 | ZZ1120 | ZZ1350 | AL1060 | ZZ1060

Version 1.7.3.185 - 11/2020

  • Name
  • Size
  • Type
  • Description
  • Name LR DEVICE
  • Size 461.2 MB
  • Type .zip
  • Description Parameter setting of IO-Link masters and sensors. Without license key – free of charge software for parameter setting for IO-Link Master AL1xxx

Videos