MVQ301

MVQ3360-XRKG/IO/B-Port/2SV/US

Positioner for industrial valves

MVQ301

MVQ3360-XRKG/IO/B-Port/2SV/US

  • Integrated adjustment algorithm with self-optimisation for positioning of industrial valves accurate to a percentage
  • Automatic Teach-In function for fast set-up
  • Reduced wiring due to direct control of the control valve
  • Self-diagnostics regarding wear, blockages or deposits for preventive maintenance
  • Individually adjustable RGB LED with flashing mode for easy visual localisation in challenging environments

To ensure the correct functioning of the device, we strongly recommend purchasing one of the complete positioner sets for the initial setup. Click here for an overview.

  • ce
  • ukca
Product characteristics
Communication interface IO-Link
Housing rectangular
Dimensions [mm] 95 x 50 x 57
solenoid valve connection (SV1 / SV2)
Electrical design PNP
Output function 2 x normally open
Application
Operating principle magnetic
Application angle of rotation detection absolute; position control
Electrical data
Protection class III
Reverse polarity protection yes
Max. power-on delay time [ms] 300
actuator supply (UA)
Operating voltage [V] 20...30 DC
Current consumption [mA] < 410
Sensor supply (US)
Operating voltage [V] 20...30 DC
Current consumption [mA] < 40
Outputs
solenoid valve connection (SV1 / SV2)
Electrical design PNP
Output function 2 x normally open
Max. current load per output [mA] 200
Short-circuit protection yes
Overload protection yes
Detection zone
Detection zone [°] 360
Accuracy / deviations
rotational angle detection
Accuracy [°] ± 1
Temperature drift [°/K] 0,02
Repeatability [°] 0,1
position control
Deadband
0,5...25 % (Factory setting: 2 %)
Resolution [%] 0,1; (preset value)
switch point indication
Hysteresis [%] 0.4...10; (Factory setting: 1 %)
Open
1...100 % (Factory setting: 95 %)
Closed
0,0...99,0 % (Factory setting: 5 %)
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9 CDV
Profiles
Function class Designation
0x0030 BLOB transfer
0x4000 Identification and Diagnosis
0x8101 Locator
0x8102 ProductURI
SIO mode no
Required master port type B
Min. process cycle time [ms] 6
Supported DeviceIDs
Type of operation DeviceID
default 1775
Operating conditions
Ambient temperature [°C] -25...70
Protection IP 65; IP 67; (Target puck area dust-protected)
Tests / approvals
EMC
EN 61000-4-2 4 kV CD / 8 kV AD
EN 61000-4-3 10 V/m
EN 61000-4-4 2 kV
EN 61000-4-6 10 V
EN 55011 class B
Vibration resistance
EN 60068-2-6 Fc 1 mm (10...55 Hz) / 1 octave per minute in 3 axes
Shock resistance
EN 60068-2-27 Ea 30 g 11 ms half sine; 6 shocks each in every direction along the three coordinate axes
MTTF [years] 421
Embedded software included yes
Mechanical data
Weight [g] 188.8
Housing rectangular
Dimensions [mm] 95 x 50 x 57
Materials housing, target puck: PA; plug, socket: stainless steel (316L / 1.4404)
Tightening torque [Nm] target puck 1,2 Nm; housing 3,0 Nm; housing on plastic mounting plate 0,9 Nm
Displays / operating elements
Display
operation 1 x LED, green
switching status 3 x LED, white
switching status 1 x LED, RGB
Accessories
Items supplied
socket head screws: 4 x M5 x 16
Remarks
Pack quantity 1 pcs.