Product characteristics
Number of inputs and outputs | Number of analogue outputs: 1 |
---|---|
Process connection | threaded connection G 1 1/2 internal thread |
Application
Special feature | Gold-plated contacts | |
---|---|---|
Media | conductive liquids | |
Note on media |
|
|
Cannot be used for | See the operating instructions, chapter "Function and features". | |
Medium temperature [°C] | -5...60 | |
Pressure rating [bar] | 10 | |
Note on pressure rating |
|
|
Vacuum resistance [mbar] | -1000 |
Electrical data
Operating voltage [V] | 18...30 DC |
---|---|
Current consumption [mA] | < 100 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 2 |
Measuring principle | inductive |
Inputs / outputs
Number of inputs and outputs | Number of analogue outputs: 1 |
---|
Outputs
Total number of outputs | 1 |
---|---|
Output signal | analogue signal; IO-Link |
Output function | selectable conductivity / temperature / NaCl concentration |
Number of analogue outputs | 1 |
Analogue current output [mA] | 4...20; (scalable) |
Max. load [Ω] | 500 |
Measuring/setting range
Measuring range [%] | 0...25; (Medium temperature: 20...50 °C) |
---|
Measuring range [µS/cm] | 100...2000000 | ||||||
---|---|---|---|---|---|---|---|
Resolution [µS/cm] |
|
Measuring range [°C] | -25...100 |
---|
Accuracy / deviations
Accuracy [%] |
|
||||||||
---|---|---|---|---|---|---|---|---|---|
Resolution [%] | 0,1 |
Accuracy (in the measuring range) | 2 % MW ± 25 µS/cm |
---|---|
Drift [%/K] | 0,1 %/K MW |
Repeatability | 1 % MW ± 25 µS/cm |
Long-term stability | 0,5 % MW ± 25 µS/cm |
Accuracy [K] |
|
||||
---|---|---|---|---|---|
Repeatability [K] | 0,2 | ||||
Resolution [K] | 0.1 |
Response times
Response time [s] | < 2; (T09; Damping = 0); for conductance values <1000 µS/cm < 5s; ( T09; Damping = 0) |
---|
Response time [s] | < 120; (T09) |
---|
Interfaces
Communication interface | IO-Link | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Transmission type | COM2 (38,4 kBaud) | ||||||||||
IO-Link revision | 1.1 | ||||||||||
SDCI standard | IEC 61131-9 | ||||||||||
Profiles |
|
||||||||||
SIO mode | no | ||||||||||
Required master port type | A | ||||||||||
Process data analogue | 1 | ||||||||||
Min. process cycle time [ms] | 6.4 | ||||||||||
IO-Link process data (cyclical) |
|
||||||||||
IO-Link functions (acyclical) | NaCl concentration; Speicher; operating hours counter; internal temperature; simulation function | ||||||||||
Supported DeviceIDs |
|
Operating conditions
Ambient temperature [°C] | -25...50 |
---|---|
Storage temperature [°C] | -25...75 |
Protection | IP 68; IP 69K; (7 days / 3 m water depth / 0.3 bar: IP 68) |
Tests / approvals
EMC |
|
||
---|---|---|---|
Shock resistance |
|
||
Vibration resistance |
|
||
MTTF [years] | 127 |
Mechanical data
Weight [g] | 404.4 |
---|---|
Materials | housing: PP reinforced fibre; Lock nut: PP reinforced fibre |
Materials (wetted parts) | housing: PP reinforced fibre; Lock nut: PP reinforced fibre; O-ring: EPDM |
Process connection | threaded connection G 1 1/2 internal thread |
Surface characteristics Ra/Rz of the wetted parts | Ra: < 0.8 |
Remarks
Remarks |
|
|
---|---|---|
Pack quantity | 1 pcs. |
Electrical connection
Connection | Connector: 1 x M12 (EN 61067-2-101); coding: A; Contacts: gold-plated |
---|
Diagrams and graphs
characteristic line for derating
|
|
---|