You probably do not come from: Canada. If necessary, change to: United States
Service hotline 855-436-2262
  1. Products
  2. AC007A

AS-Interface ClassicLine module

AC007A

ClassicL45 2DI 2DO T M12

AS-Interface ClassicLine module

AC007A

ClassicL45 2DI 2DO T M12

Article no longer available - archive entry
Alternative articles: AC507A + E7000A Product comparison: AC007A / AC507A When selecting an alternative article and accessories please note that technical data may differ!
  • ce
  • ex
  • asib
Electrical data
Operating voltage [V] 26.5...31.6 DC
Max. current consumption from AS-i [mA] 150
Max. current load total [A] 2
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital inputs: 2; Number of digital outputs: 2
Inputs
Number of digital inputs 2
Input circuit of digital inputs PNP
Sensor supply of the inputs AS-i
Power supply [V] 18...30
Max. total current rating of inputs [mA] 100
Input current High [mA] 6...10
Input current Low [mA] 0...2
Switching level high [V] > 11
Digital inputs protected against short circuits yes
Outputs
Electrical design AS-i
Number of digital outputs 2
Circuit PNP
Voltage range DC [V] 15...30; (to PELV)
Max. current load per output [mA] 1000; (utilisation category DC-13 (control of electromagnets): 20 W (IEC 60947-5-1))
Short-circuit proof yes
Electrically separated yes
Operating conditions
Ambient temperature [°C] 0...40
Protection IP 67
Tests / approvals
ATEX marking II 3G EEx nA II T6 X
II 3D T60 °C IP 67 X
EMC
EN 50295
AS-i classification
AS-i profile S-3.0.E
AS-i I/O configuration [hex] 3
AS-i ID code [hex] 0.E
AS-i certificate pending yes
Assignment of the data bits
data bit D0 D1 D2 D3
socket I-1 I-2 O-3 O-4
pin 2+4 2+4 4 4
Mechanical data
Type of mounting AS-i interface to FC-E lower parts
Dimensions [mm] 45 x 83 x 25
Materials PBT
Displays / operating elements
Display
operation LED, green
errors LED, red
function LED, yellow
Accessories
Items supplied
AC5003
Remarks
Remarks
Inputs and outputs must be electrically isolated.
Do not connect any of the following points to an external potential:
I-, I+, I1, I2
The connections are electrically connected with the AS-i cable.
Use M12 connectors with hexagon nuts, tightening torque 0.8 Nm.
Pack quantity 1 pcs.
Electrical connection
contact pins to module lower part, FK-E:
Connector: M12; coding: A