Product characteristics |
Number of inputs and outputs |
Number of digital outputs: 2 |
Measuring range |
350...1350 °C |
662...2462 °F |
|
Application |
Application |
tempering temperatures; graphite; ceramics; metals; forging; sintering; heat treatment; rolling |
Electrical data |
Operating voltage [V] |
10...34 DC |
Current consumption [mA] |
30; (24 V) |
Protection class |
III |
Inputs / outputs |
Number of inputs and outputs |
Number of digital outputs: 2 |
Inputs |
Test input |
test function active at U(test) > 9 V |
Outputs |
Total number of outputs |
2 |
Output signal |
switching signal |
Electrical design |
PNP |
Number of digital outputs |
2 |
Output function |
normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] |
2.5 |
Permanent current rating of switching output DC [mA] |
150 |
Short-circuit protection |
yes |
Type of short-circuit protection |
pulsed |
Overload protection |
yes |
Detection zone |
Wave length range [µm] |
1...1.7 |
Measuring/setting range |
Measuring range |
350...1350 °C |
662...2462 °F |
|
Factory setting |
SP1 = 25 %; rP1 = 23 %; SP2 = 75 %; rP2 = 73 % |
Set point SP |
350...1340 °C |
662...2444 °F |
|
Reset point rP |
350...1340 °C |
662...2444 °F |
|
In steps of |
|
Resolution |
Resolution of switching output [K] |
10 |
Resolution of display [K] |
10 |
Accuracy / deviations |
Accuracy [K] |
< ± 1 %; (of VMR (degree of emission = 1 and T = 23 °C)) |
Response times |
Response time [ms] |
2 |
Software / programming |
Adjustment of the switch point |
programming buttons |
Parameter setting options |
Hysteresis; normally open / normally closed; switch-on/switch-off delay |
Operating conditions |
Ambient temperature [°C] |
0...65 |
Storage temperature [°C] |
-20...80 |
Max. relative air humidity [%] |
95; (non condensing) |
Protection |
IP 65 |
Tests / approvals |
EMC |
DIN EN 61000-4-2 ESD |
4 kV CD / 8 kV AD |
DIN EN 61000-4-3 HF radiated |
10 V/m |
DIN EN 61000-4-4 Burst |
2 kV coupling clamp |
DIN EN 61000-4-5 Surge |
0,5 / 1 kV |
DIN EN 61000-4-6 HF conducted |
10 V |
EN 55011 emission |
class B |
|
Shock resistance |
DIN EN 60068-2-27 |
30 g (11 ms) |
|
Vibration resistance |
DIN EN 60068-2-6 |
5 g (10...2000 Hz) |
|
MTTF [years] |
117 |
Mechanical data |
Weight [g] |
374 |
Housing |
threaded type |
Dimensions [mm] |
M30 x 1.5 / L = 163 |
Thread designation |
M30 x 1.5 |
Fibre optic connection |
¼"-36UNS-2A |
Materials |
threaded sleeve: stainless steel (1.4305 / 303); polyester |
Lens material |
|
Displays / operating elements |
Display |
switching status |
2 x LED, yellow |
function display |
7-segment LED display, 2-digit |
measured values |
7-segment LED display, 2-digit |
|
Operating elements |
|
Accessories |
Items supplied |
|
Accessories (optional) |
fibre optics:, E35061 / E35062 |
Measuring head:, E35060 |
|
Remarks |
Remarks |
MW = measured value |
MEW = Final value of the measuring range |
|
Pack quantity |
1 pcs. |
Electrical connection |
Connection |
Connector: 1 x M12 |