industrial gas counter

SD8600

SDR11DGXFRKG/US-100

industrial gas counter

SD8600

SDR11DGXFRKG/US-100

  • Precise measurement of flow, consumption, pressure and medium temperature
  • High accuracy, repeatability and measurement dynamics
  • For detecting argon (Ar), carbon dioxide (CO2), nitrogen (N2) and compressed air
  • Red/green display for clear identification of the acceptable range
  • Display can be rotated for optimum alignment
  • Convenient operation via buttons or parameter setting via IO-Link
  • dnv_gl
  • ce
  • ukca
  • iolink
  • cul
  • crn
Product characteristics
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Measuring range
14...3750 l/min 0.4...103.7 m/s 0.8...225 m³/h
Process connection threaded connection R 1 DN25
Application
Application for industrial applications
Media Argon (Ar); carbon dioxide (CO2); nitrogen (N2); compressed air
Medium temperature [°C] -10...60
Min. bursting pressure [bar] 64
Min. bursting pressure [MPa] 6.4
Pressure rating [bar] 16
Pressure rating [MPa] 1.6
MAWP (for applications according to CRN) [bar] 10.5
Electrical data
Operating voltage [V] 18...30 DC; (to SELV/PELV)
Current consumption [mA] < 80
Protection class III
Reverse polarity protection yes
Power-on delay time [s] 1
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Inputs
Inputs counter reset
Outputs
Output signal switching signal; analogue signal; pulse signal; IO-Link; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V] 2.5
Permanent current rating of switching output DC [mA] 150; (per output)
Number of analogue outputs 1
Analogue current output [mA] 4...20; (scalable)
Max. load [Ω] 500
Pulse output consumed quantity meter
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
Measuring/setting range
Measuring range
14...3750 l/min 0.4...103.7 m/s 0.8...225 m³/h
Display range
0...4500 l/min 0...124.4 m/s 0...270 m³/h
Resolution
2 l/min 0.1 m/s 0.1 m³/h
Set point SP
32...3749 l/min 0.9...103.7 m/s 1.9...224.9 m³/h
Reset point rP
14...3730 l/min 0.4...103.2 m/s 0.8...223.8 m³/h
Analogue start point ASP
0...3000 l/min 0...83 m/s 0...180 m³/h
Analogue end point AEP
750...3750 l/min 20.7...103.7 m/s 45...225 m³/h
Low flow cut-off LFC
4...40 l/min 0.1...1.1 m/s 0.3...2.4 m³/h
In steps of
1 l/min 0.1 m/s 0.1 m³/h
Pressure monitoring
Measuring range [bar] -1...16
Display range [bar] -1...20
Resolution [bar] 0.05
Set point SP [bar] -0.92...16
Reset point rP [bar] -1...15.92
Analogue start point [bar] -1...12.8
Analogue end point [bar] 2.2...16
In steps of [bar] 0.01
Volumetric flow quantity monitoring
Measuring range
0...100000000 m³ 0...353146667.2 scf
Display range
0...100000000 m³ 0...353146667.2 scf
Set point SP
0.001...10000000 m³ 0.05...353146667.2 scf
Pulse value
0.001...10000000 m³ 0.05...353146667.2 scf
In steps of
0.0001 m³ 0.005 scf
Pulse length [s] 0.007...2
Temperature monitoring
Measuring range
-10...60 °C 14...140 °F
Display range
-24...74 °C -11.2...165.2 °F
Resolution
0.2 °C 0.5 °F
Set point SP
-9.7...60 °C 14.6...140 °F
Reset point rP
-10...59.7 °C 14...139.4 °F
Analogue start point
-10...46 °C 14...114.8 °F
Analogue end point
4...60 °C 39.2...140 °F
In steps of
0.1 °C 0.1 °F
Accuracy / deviations
Temperature coefficient [1/K] ± 0,07 % MW
Accuracy (in the measuring range) ± (6 % MW + 0,6 % MEW); at medium temperature 23 °C
Repeatability ± (0,4 % MW + 0,1 % MEW)
Pressure monitoring
Repeatability [% of the final value] ± 0,2
Characteristics deviation [% of the final value] < ± 0,5; (BFSL = Best Fit Straight Line)
Greatest TEMPCO of the span [% MEW / 10 K] ± 0,3
Greatest TEMPCO of the zero point [% MEW / 10 K] ± 0,1
Temperature monitoring
Accuracy [K] ± 0,5; (medium flow in the limit area of the flow measurement range)
Response times
Response time [s] 0.1; (dAP = 0)
Damping process value dAP [s] 0...5
Pressure monitoring
Response time [s] 0.05
Temperature monitoring
Dynamic response T05 / T09 [s] T09 = 0,5
Software / programming
Parameter setting options hysteresis / window; normally open / normally closed; current/pulse output; display can be rotated and switched off; Display unit; totaliser
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9 CDV
Profiles Digital Measuring Sensor (0x800A), Identification and Diagnosis (0x4000)
SIO mode yes
Required master port type A
Process data analogue 8
Process data binary 2
Min. process cycle time [ms] 7.2
Supported DeviceIDs
Type of operation DeviceID
default 868
Operating conditions
Ambient temperature [°C] 0...60
Storage temperature [°C] -20...85
Max. relative air humidity [%] 90
Protection IP 65; IP 67
Tests / approvals
EMC
DIN EN 60947-5-9
CPA approval
model number 003TG
accuracy class -
maximum allowable error ± 7 % FS
Q (min) 0,8 m³/h
Q (t) -
Q (max) 225 m³/h
Vibration resistance
DIN EN 68000-2-6 5 g (10...2000 Hz)
MTTF [years] 183
UL approval
UL Approval no. I012
File number UL E174189
Pressure Equipment Directive Sound engineering practice; can be used for stable gases fluid group 2
Mechanical data
Weight [g] 1609
Materials PBT+PC-GF30; PPS GF40; stainless steel (1.4301 / 304); stainless steel (1.4305 / 303); steel (1.5523) galvanised; 2.0401 (brass / CW614N); FKM
Materials (wetted parts) stainless steel (1.4301 / 304); stainless steel (1.4305 / 303); FKM; ceramics glass passivated; PPS GF40; Al2O3 (ceramics); acrylate
Process connection threaded connection R 1 DN25
Displays / operating elements
Display
colour display 1,44", 128 x 128 pixels
2 x LED, yellow
Remarks
Remarks
MW = measured value
MEW = Final value of the measuring range
Standard conditions: 1013.25 mbar / 15 °C / 0 % relative humidity
For information about installation and operation please see the operating instructions.
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12; coding: A