You probably do not come from: Australia. If necessary, change to: United States
  1. Products
  2. Industrial communication
  3. AS-Interface I/O modules
  4. Field modules with quick mounting technology ClassicLine
  5. AC5215

AS-Interface ClassicLine module with quick mounting technology

AC5215

ClassicLine 4DI-Y IP67

AS-Interface ClassicLine module with quick mounting technology

AC5215

ClassicLine 4DI-Y IP67

  • Easy toolless installation and wiring thanks to quick mounting technology
  • Three freely selectable directions of the flat cable
  • Clearly visible powerful LEDs for displaying operation, switching status and error
  • High protection rating for the requirements of harsh industrial environments
  • Robust M12 connectors for connecting sensors and actuators
  • ce
  • ukca
  • asib
  • cul
Application
Application field installation
Electrical data
Operating voltage [V] 26.5...31.6 DC
Max. current consumption from AS-i [mA] 250
Inputs / outputs
Number of inputs and outputs Number of digital inputs: 4
Inputs
Number of digital inputs 4
Input circuit of digital inputs PNP
Sensor supply of the inputs AS-i
Power supply [V] 18...30; (DC)
Max. total current rating of inputs [mA] 200
Input current High [mA] 6...10
Input current Low [mA] 0...2
Switching level high [V] > 11
Digital inputs protected against short circuits yes
Operating conditions
Ambient temperature [°C] -25...70
Protection IP 67
Tests / approvals
EMC
EN 50295
IEC 61000-6-2
MTTF [years] 405
AS-i classification
AS-i version 2.11; 3.0
AS-i addressing addressing socket
Extended addressing mode yes
AS-i master profile M2; M3; M4
AS-i profile S-0.A.E
AS-i I/O configuration [hex] 0
AS-i ID code [hex] A.E
Assignment of the data bits
data bit D0 D1 D2 D3
input 1 2 3 4
socket I-1/2 I-1/2 I-2 I-3/4 I-3/4 I-4
pin 4 2 4 4 2 4
Mechanical data
Weight [g] 155.6
Type of mounting AS-i flat cables directly connectable
Materials PA; piercing contacts: CuSn6 nickel-plated and tin-plated
Displays / operating elements
Display
operation LED, green
errors LED, red
function LED, yellow
Electrical connection
Module connection Flat cables
Accessories
Items supplied
lower part
Accessories (optional)
Protective cap: M12, E73004
Remarks
Remarks
Do not connect any of the following points to an external potential:
I-, I+, I-1/2, I-2, I-3/4, I-4
The connections are electrically connected with the AS-i cable.
operating voltage "supply class 2" according to cULus
Pack quantity 1 pcs.
Electrical connection
Connection quick mounting technology for AS-i flat cable: ; three orientations possible
Connection Connector: M12