Application
Application |
field installation |
Electrical data
Operating voltage [V] |
26.5...31.6 DC |
Max. current consumption from AS-i [mA] |
250 |
Max. current load total [A] |
4 |
Additional voltage supply [V] |
10...30 DC; (AUX) |
Max. current consumption from additional supply [mA] |
4000; (AUX) |
Integrated watchdog |
yes |
Inputs / outputs
Number of inputs and outputs |
Number of digital inputs: 4; Number of digital outputs: 4 |
Inputs
Number of digital inputs |
4 |
Input circuit of digital inputs |
PNP; (type 2 according to IEC 61131-2) |
Sensor supply of the inputs |
AS-i |
Power supply [V] |
20...30; (DC) |
Max. total current rating of inputs [mA] |
200 |
Input current limitation [mA] |
15 |
Input current High [mA] |
6...10 |
Input current Low [mA] |
0...2 |
Switching level high [V] |
> 11 |
Digital inputs protected against short circuits |
yes |
Outputs
Number of digital outputs |
4 |
Circuit |
PNP |
Voltage range DC [V] |
10...30; (AUX) |
Max. current load per output [mA] |
2000; (utilisation category DC-13 (control of electromagnets): 20 W (IEC 60947-5-1)) |
Max. current load outputs total [A] |
4 |
Short-circuit proof |
yes |
Electrically separated |
yes |
Actuator supply outputs |
AUX |
Operating conditions
Ambient temperature [°C] |
-25...80 |
Storage temperature [°C] |
-25...80 |
Max. relative air humidity [%] |
90; (non condensing) |
Max. height above sea level [m] |
2000 |
Protection |
IP 67; (when flat cables are used E7400x / E7401x) |
Tests / approvals
EMC |
EN 61000-6-2 |
|
EN 62026-2 |
|
EN 50581 |
|
|
MTTF [years] |
193 |
UL approval |
|
AS-i classification
AS-i version |
2.11; 3.0 |
AS-i addressing |
IR addressing possible |
Extended addressing mode |
no |
AS-i master profile |
M2; M3; M4 |
AS-i profile |
S-7.0.E |
AS-i I/O configuration [hex] |
7 |
AS-i ID code [hex] |
0.E |
AS-i certificate |
46001 |
Assignment of the data bits |
data bit |
D0 |
D1 |
D2 |
D3 |
input |
1 |
2 |
3 |
4 |
socket |
I-1 |
I-2 |
I-3 |
I-4 |
pin |
2+4 |
2+4 |
2+4 |
2+4 |
Output |
1 |
2 |
3 |
4 |
socket |
O-1 |
O-2 |
O-3 |
O-4 |
pin |
4 |
4 |
4 |
4 |
|
Mechanical data
Weight [g] |
386 |
Materials |
PA; socket: brass nickel-plated; O-ring: FKM |
Displays / operating elements
Display |
switching status |
LED, yellow I1...I4, O1...O4 |
operation |
LED, green AS-i, AUX |
errors |
LED, red |
|
Accessories
Accessories (optional) |
Stainless steel sleeve, for installation in case of high mechanical stress , E70402 |
|
Remarks
Remarks |
Do not connect any of the following points to an external potential: |
I-, I+, I1, I2, I3, I4 |
The connections are electrically connected with the AS-i cable. |
|
Pack quantity |
1 pcs. |
Electrical connection - AS-i
|
Connector: M12; coding: A |
Electrical connection - Inputs
|
Connector: M12; coding: A |
Electrical connection - Outputs
|
Connector: M12; coding: A |