Product characteristics
Electrical design | PNP/NPN; (parameterisable) |
---|---|
Communication interface | IO-Link |
Dimensions [mm] | 250 x 28 x 16.7 |
Application
Application | Continuous level measurement behind non-metallic and non-conductive surfaces |
---|---|
Media | dry bulk material; aqueous solutions; oils |
Cannot be used for | highly adhesive media |
Electrical data
Operating voltage [V] | 10...30 DC; (IO-Link: 18...30 DC) |
---|---|
Current consumption [mA] | < 50 |
Protection class | III |
Reverse polarity protection | yes |
Max. power-on delay time [ms] | 1300 |
Measuring principle | capacitive |
Inputs / outputs
Number of inputs and outputs | Number of digital outputs: 3 |
---|
Outputs
Electrical design | PNP/NPN; (parameterisable) |
---|---|
Number of digital outputs | 3 |
Permanent current rating of switching output DC [mA] | 200 |
Max. resistance switching output [Ω] | 8 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Detection zone
Measuring range [mm] | < 200 |
---|
Measuring/setting range
Detection range [mm] | 228 |
---|---|
Set point SP [%] | 5...95 |
Reset point rP [%] | 4...94 |
In steps of [%] | 1 |
Accuracy / deviations
Repeatability [% of the final value] | 2 |
---|---|
Offset deviation [% of the final value] | 4 |
Resolution [% of the final value] | 1 |
Linearity deviation [% of the final value] | 1 |
Response times
Response time [ms] | 1300 |
---|
Interfaces
Communication interface | IO-Link | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Transmission type | COM2 (38,4 kBaud) | ||||||||||
IO-Link revision | 1.1 | ||||||||||
SDCI standard | IEC 61131-9 | ||||||||||
Profiles | Digital Measuring Sensor Profile, Common Profile | ||||||||||
SIO mode | yes | ||||||||||
Required master port type | A | ||||||||||
Process data analogue | 1 | ||||||||||
Process data binary | 3 | ||||||||||
Min. process cycle time [ms] | 9.6 | ||||||||||
IO-Link process data (cyclical) |
|
||||||||||
IO-Link functions (acyclical) | direction of installation; limitation of sensor elements; sensitivity; minimum recognition threshold; Performance in case of a fault; error delay; Damping; LED mode; switch-on cycle counter; operating hours counter; switching cycles counter; min./max. process value; internal temperature; min./max. internal temperature; diagnostic data for level | ||||||||||
Supported DeviceIDs |
|
||||||||||
Note |
|
Operating conditions
Applications | DIN EN 60654-1 application class B2 |
---|---|
Ambient temperature [°C] | -20...80 |
Storage temperature [°C] | -25...85 |
Protection | IP 65 |
Tests / approvals
EMC |
|
||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Shock resistance |
|
||||||||||||||
Vibration resistance |
|
||||||||||||||
MTTF [years] | 290.43 | ||||||||||||||
UL approval |
|
Mechanical data
Weight [g] | 432 |
---|---|
Dimensions [mm] | 250 x 28 x 16.7 |
Materials | PBT; PC; |
Displays / operating elements
Display |
|
---|
Accessories
Items supplied |
|
||||
---|---|---|---|---|---|
Accessories (optional) |
|
Remarks
Remarks |
|
|
---|---|---|
Pack quantity | 1 pcs. |
Electrical connection
Connection | Cable: 2 m, PUR; 5 x 0.34 mm² |
---|