Electrical data
Operating voltage [V] |
18...30 DC |
Current consumption [mA] |
100; (US) |
Protection class |
III |
Additional voltage supply [V] |
18...30 DC; (UA) |
Max. current consumption from additional supply [mA] |
3600; (UA) |
Inputs / outputs
Total number of inputs and outputs |
16 |
Number of inputs and outputs |
Number of digital inputs: 16; Number of digital outputs: 16 |
Inputs
Number of digital inputs |
16; (configurable) |
Input circuit of digital inputs |
PNP; (type 3 (IEC 61131-2)) |
Sensor supply of the inputs |
UA |
Power supply [V] |
18...30 |
Input current High [mA] |
2...15 |
Input current Low [mA] |
0...1.5 |
Switching level high [V] |
11...28 |
Switching level low [V] |
0...5 |
Outputs
Number of digital outputs |
16; (configurable) |
Max. current load per output [mA] |
1800 |
Max. current load outputs total [A] |
3.6; (max. current load per segment: 1800 mA) |
Short-circuit protection |
yes |
Actuator supply outputs |
UA |
Interfaces
Communication interface |
IO-Link |
SDCI standard |
IEC 61131-9 |
Transmission type |
COM3 (230,4 kBaud) |
IO-Link revision |
1.1 |
SIO mode |
no |
Required master port type |
B |
Min. process cycle time [ms] |
4 |
Supported DeviceIDs |
Type of operation |
DeviceID |
default |
1409 |
|
Note |
For further information please see the IODD PDF file under "Downloads" |
|
Operating conditions
Ambient temperature [°C] |
-25...60 |
Storage temperature [°C] |
-25...70 |
Max. relative air humidity [%] |
90 |
Max. height above sea level [m] |
2000 |
Protection |
IP 65; IP 67; IP 69K; (operation with stainless steel protective caps: IP 69K) |
Protection rating (NEMA 250) |
6P |
Pollution degree |
2 |
Chemical media |
ISO 16750-5 |
HLP, CC, DB, DC, DD, CA |
NEMA 250 5.13.1 |
AA |
|
Tests / approvals
EMC |
EN 61000-6-2 |
|
EN 61000-6-3 |
|
IEC 61131-9 |
|
|
Shock resistance |
|
Vibration resistance |
DIN EN 60068-2-64 |
|
DIN EN 60068-2-6 |
|
|
Mechanical data
Weight [g] |
482.326 |
Dimensions [mm] |
26 x 59.3 x 208 |
Materials |
housing: PA grey; socket: stainless steel (316L/1.4404) |
Sealing material |
EPDM |
Displays / operating elements
Display |
operation |
1 x LED, green |
fault |
1 x LED, red |
function |
1 x LED, yellow |
|
Accessories
Accessories (optional) |
protective cap for M12 sockets |
|
Electrical connection - IO-Link
X1 |
Connector: 1 x M12; coding: A |
Electrical connection - inputs / outputs
X1.0...X1.7 |
Connector: 8 x M12; coding: A; Sealing: EPDM |