Application
Application |
field installation; for use in wet environments |
Electrical data
Operating voltage [V] |
26.5...31.6 DC |
Max. current consumption from AS-i [mA] |
150 |
Integrated watchdog |
yes |
Inputs / outputs
Number of inputs and outputs |
Number of digital inputs: 2; Number of pneumatic outputs: 2 |
Inputs
Number of digital inputs |
2 |
Input circuit of digital inputs |
PNP |
Sensor supply of the inputs |
AS-i |
Power supply [V] |
20...30 |
Max. total current rating of inputs [mA] |
100 |
Input current High [mA] |
> 3 |
Input current Low [mA] |
< 1.5 |
Switching level high [V] |
> 10 |
Digital inputs protected against short circuits |
yes |
Outputs
Number of pneumatic outputs |
2 |
Actuator supply outputs |
AS-i |
Operating conditions
Ambient temperature [°C] |
0...55 |
Note on ambient temperature |
with special compressed air treatment: < 0 °C |
the derating of the current load indicated in the operating instructions is to be taken into account at the following ambient temperature: > 50 °C |
|
Storage temperature [°C] |
-20...80 |
Max. relative air humidity [%] |
90; (non condensing) |
Max. height above sea level [m] |
2000 |
Protection |
IP 67 |
Pollution degree |
2 |
Tests / approvals
EMC |
EN 62026-2 |
|
EN IEC 61000-6-2 |
|
EN IEC 61000-6-4 |
|
EN IEC 61326-1 |
|
|
AS-i classification
Extended addressing mode |
no |
AS-i master profile |
M2; M3; M4 |
AS-i profile |
S-3.F.F |
AS-i I/O configuration [hex] |
3 |
AS-i ID code [hex] |
F.F |
Assignment of the data bits |
data bit |
D0 |
D1 |
D2 |
D3 |
Inputs / outputs |
I-1 |
I-2 |
O-3 |
O-4 |
|
Mechanical data
Weight [g] |
254.5 |
Type of mounting |
screw mounting |
Dimensions [mm] |
45 x 80 x 46 |
Materials |
PBT |
Pneumatic system |
2 x 3/2-way seat valves |
Operating pressure range [bar] |
2...8 |
Note on working pressure range |
incl. possible pressure peaks |
|
Air flow at 6/5 bar [l/min] |
350 |
Air flow at 6/0 bar [l/min] |
550 |
Permissible compressed air |
filtered (5 µm); lubricated (ISO-VG10) or not lubricated |
Tube fittings |
Legris LF 3000/8 |
Exhaust |
exhaust can be discharged through tube connection |
Displays / operating elements
Display |
operation |
LED, green (AS-i) |
switching status |
LED, yellow (I1...I2, O3...O4) |
|
Electrical connection
Module connection |
Flat cables |
Remarks
Remarks |
Please see the notes on compressed air and EMC/ESD under "Downloads" |
|
Pack quantity |
1 pcs. |
Electrical connection - socket I-1
|
contact pins to module lower part, FK / PG: |
|
Connector: M12; coding: A |
Electrical connection - socket I-2
|
contact pins to module lower part, FK / PG: |
|
Connector: M12; coding: A |