Electrical data
Operating voltage tolerance [%] | 10 |
---|---|
Nominal voltage AC [V] | 110 / 230 |
Nominal frequency AC [Hz] | 47...63 |
Input voltage range AC [V] | 100...240 |
Protection class | I |
Overvoltage protection | yes; (< 34 V) |
Max. power-on delay time [ms] | 150 |
Output voltage AS-i [V] | 29.5...31.6; (to PELV; NEC Class II) |
Number of output circuits | 1 |
Output current AS-i [A] | 2.8 |
Max. residual ripple [mV] | 50 |
Efficiency (nominal voltage 230 V AC / 50 Hz) [%] | 88 |
External input protection | 10 A; B |
Derating [W/K] | 3% / K (> 60° C) |
Mains buffering time (nominal voltage 230 V AC / 50 Hz) [ms] | 330 |
Integrated data decoupling | yes |
Outputs
Short-circuit proof | yes |
---|---|
Overload protection | yes |
Parallel connection of outputs possible | no |
Series connection of outputs possible | no |
Operating conditions
Ambient temperature [°C] | 0...70 |
---|---|
Protection | IP 20 |
Tests / approvals
EMC |
|
---|
AS-i classification
AS-i certificate | 89502 |
---|
Mechanical data
Weight [g] | 984.5 |
---|---|
Type of mounting | rail; (TH35 (EN 60715); free space for convection cooling 20 mm) |
Dimensions [mm] | 136 x 50 x 144 |
Materials | AlMg3; steel sheet galvanised; PC |
Displays / operating elements
Display |
|
---|
Remarks
Pack quantity | 1 pcs. |
---|
Electrical connection
Connection | screw terminals: |
---|