Number of inputs and outputs | Number of analog outputs: 2 |
---|
System | gold-plated contacts |
---|
Operating voltage [V] | 12...30 DC |
---|---|
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | < 1 |
Measuring principle | capacitive |
Number of inputs and outputs | Number of analog outputs: 2 |
---|
Total number of outputs | 2 |
---|---|
Output signal | analog signal |
Number of analog outputs | 2 |
Analog current output [mA] | 4...20 |
Max. load [Ω] | (Ub - 12 V) / 20 mA |
Measuring range [% RH] | 0...100 |
---|
Measuring range [°C] | -40...60 |
---|
Accuracy [% RH] | 4; (in the range 20...80 % RH) |
---|---|
Resolution [% RH] | 0,1 |
Accuracy [K] | ± 1 |
---|---|
Resolution [K] | 0.1 |
Response time [s] | < 30; (T90) |
---|
Response time [s] | < 300; (T90) |
---|
Ambient temperature [°C] | -40...70 | ||
---|---|---|---|
Note on ambient temperature |
|
||
Storage temperature [°C] | -40...85 | ||
Note on storage temperature |
|
||
Protection | IP 20; (only sensor: IP 57) |
EMC |
|
||||
---|---|---|---|---|---|
MTTF [years] | 178 | ||||
UL approval |
|
Weight [g] | 72.3 |
---|---|
Type of mounting | DIN rail clip for 35 mm DIN rail (EN 60715); screw mounting; (M5) |
Dimensions [mm] | 140 x 40 x 38 |
Material | plastics UL94 V-0; light grey |
Mounting orientation | vertical; connector facing upwards |
Pack quantity | 1 pcs. |
---|
Connection | Connector: 1 x M12 (EN 61067-2-101); coding: A; Contacts: gold-plated |
---|