Dimensions [mm] | 48 x 112 x 116 |
---|
Application | displaying and monitoring analog signals; e.g. pressure sensors, temperature sensors or flow sensors |
---|
Frequency AC [Hz] | 50...60 |
---|---|
Operating voltage [V] | 115...230 AC / 18...30 DC |
Current consumption [mA] | 100 |
Power consumption [W] | 3 |
Number of inputs and outputs | Number of analog inputs: 2; Number of digital outputs: 4; Number of analog outputs: 1 |
---|
Number of analog inputs | 2; (Spannungs- oder Stromeingang) |
---|---|
Analog input (current) [mA] | 0...20 |
Analog input (voltage) [V] | -10...10 |
Resolution of analog input | 16 bit |
Precision analog input [%] | 0,1 |
Number of digital outputs | 4 |
---|---|
Max. current load per output [mA] | 200 |
Number of analog outputs | 1 |
Analog current output [mA] | 0...20 |
Max. load [Ω] | 270 |
Analog voltage output [V] | -10...10 |
Precision analog output [%] | 0,1 |
Overload protection | yes |
Resolution of analog output | 16 bit |
Ambient temperature [°C] | -20...60 |
---|---|
Storage temperature [°C] | -25...70 |
Protection | IP 65 |
Protection rating terminals | IP 20 |
EMC |
|
---|
Weight [g] | 350.5 |
---|---|
Type of mounting | panel cutout: 91 x 43 mm |
Dimensions [mm] | 48 x 112 x 116 |
Material | Noryl UL94-V-0 |
Display |
|
---|
Connection | screw terminals: |
---|