Electrical data |
Operating voltage [V] |
26.5...31.6 DC |
Current consumption [mA] |
< 250 |
Max. current load total [A] |
0.3 |
Integrated watchdog |
yes |
Inputs / outputs |
Number of inputs and outputs |
Number of digital inputs: 4; Number of digital outputs: 4 |
Inputs |
Number of digital inputs |
4 |
Input circuit of digital inputs |
PNP |
Sensor supply of the inputs |
AS-i |
Voltage supply [V] |
20...30 |
Max. total current rating of inputs [mA] |
140 |
Input current High [mA] |
6...10 |
Input current Low [mA] |
0...2 |
Min. switching level high signal [V] |
10 |
Digital inputs protected against short circuits |
yes |
Outputs |
Electrical design |
AS-i |
Number of digital outputs |
4 |
Voltage range DC [V] |
18...30; (to PELV) |
Voltage range AC [V] |
110...400 |
Max. current load per output [mA] |
150; (external outputs: Short-circuit proof; reversing contactor: not protected against short circuits) |
Electrically separated |
yes |
Operating conditions |
Ambient temperature [°C] |
0...60 |
Protection |
IP 54 |
Tests / approvals |
EMC |
|
AS-i classification |
AS-i version |
2.0 |
Extended addressing mode possible |
no |
AS-i profile |
S-7.0 |
AS-i I/O configuration [hex] |
7 |
AS-i ID code [hex] |
0 |
Mechanical data |
Weight [g] |
555 |
Type of mounting |
backplane mounting |
Dimensions [mm] |
180 x 182 x 90 |
Materials |
PC glass fibre reinforced; flame-retardant; UV resistant |
Displays / operating elements |
Display |
switching status |
LED, yellow |
operation |
LED, green |
errors |
LED, red |
|
Remarks |
Remarks |
The PowerSwitch motor starter uses two outputs to trigger the reversing contactors (motor right/left/off). |
Two further outputs can be connected at will. |
The messages "motor protection activated" and "hand-held operating panel connected" are indicated via the input data bits. |
Sensors can be connected to two additional inputs. |
|
Pack quantity |
1 pcs. |