Electrical data |
Operating voltage [V] |
26.5...31.6 DC; (operating voltage "supply class 2" according to cULus) |
Max. current consumption from AS-i [mA] |
30 |
Max. current load total [A] |
4 |
Integrated watchdog |
yes |
Inputs / outputs |
Number of inputs and outputs |
Number of digital inputs: 4; Number of digital outputs: 4 |
Inputs |
Number of digital inputs |
4; (bidirectional) |
Input circuit of digital inputs |
PNP |
Sensor supply of the inputs |
to PELV |
Voltage supply [V] |
20...30; (operating voltage "supply class 2" according to cULus) |
Max. total current rating of inputs [mA] |
200 |
Input current High [mA] |
6...10 |
Input current Low [mA] |
0...2 |
Min. switching level high signal [V] |
11 |
Digital inputs protected against short circuits |
yes |
Outputs |
Electrical design |
AS-i |
Number of digital outputs |
4 |
Circuit |
PNP |
Voltage range DC [V] |
20...30; (to PELV; via flat cable; operating voltage "supply class 2" according to cULus) |
Max. current load per output [mA] |
2000 |
Short-circuit proof |
yes |
Electrically separated |
yes |
Operating conditions |
Ambient temperature [°C] |
-25...70 |
Protection |
IP 67 |
Tests / approvals |
EMC |
|
AS-i classification |
AS-i version |
2.1 |
AS-i addressing |
IR addressing possible |
Extended addressing mode possible |
no |
AS-i profile |
S-7.0.E |
AS-i I/O configuration [hex] |
7 |
AS-i ID code [hex] |
0.E |
AS-i certificate pending |
yes |
Assignment of the data bits |
data bit |
D0 |
D1 |
D2 |
D3 |
bidirectional |
I-1 / O-1 |
I-2 / O-2 |
I-3 / O-3 |
I-4 / O-4 |
|
Mechanical data |
Type of mounting |
AS-i flat cables directly connectable |
Dimensions [mm] |
60 x 152 x 24 |
Materials |
PUR |
Displays / operating elements |
Display |
operation |
LED, green |
errors |
LED, red |
function |
LED, yellow |
|
Accessories |
Accessories (optional) |
Stainless steel sleeve, for installation in case of high mechanical stress , E70402 |
|
Remarks |
Pack quantity |
1 pcs. |
Electrical connection |
|
Connector: M12 |