You probably do not come from: New Zealand. If necessary, change to: United States
  1. Products
  2. AC2739

AS-Interface PCB module

AC2739

PCB 4DI 3DO T W

AS-Interface PCB module

AC2739

PCB 4DI 3DO T W

  • For installation in small housings, control cabinets and operator panels
  • Simple and fast wiring by means of wire strands
  • Particularly space-saving design
  • For integration of mechanical switches into AS-i networks
  • AS-i connection for three control and signalling devices
Article no longer available - archive entry
Alternative articles: AC2751 Product comparison: AC2739 / AC2751 When selecting an alternative article and accessories please note that technical data may differ!
  • ce
  • asib
  • cruus
Application
Application housing for panel mounting
Electrical data
Operating voltage [V] 26.5...31.6 DC
Current consumption [mA] < 170
Max. current load total [A] 0.12
Inputs / outputs
Number of inputs and outputs Number of digital inputs: 4; Number of digital outputs: 3
Inputs
Number of digital inputs 4
Input circuit of digital inputs PNP
Sensor supply of the inputs AS-i
Power supply [V] 15...29; (DC)
Input current High [mA] > 3
Input current Low [mA] < 1.5
Switching level high [V] > 10
Digital inputs protected against short circuits yes
Outputs
Electrical design PNP
Number of digital outputs 3
Circuit PNP
Max. current load per output [mA] 40
Short-circuit proof yes
Electrically separated yes
Actuator supply outputs AS-i
Operating conditions
Ambient temperature [°C] -25...60
Protection IP 20
Tests / approvals
EMC
EN 50295
AS-i classification
AS-i version 3.0
Extended addressing mode yes
AS-i master profile M2; M3; M4
AS-i profile S-7.A.E
AS-i I/O configuration [hex] 7
AS-i ID code [hex] A.E
Mechanical data
Weight [g] 115.5
Type of mounting for Moeller housing RMQ-Titan: I3M, I4M, I6M
Displays / operating elements
Display
operation LED, green
Remarks
Remarks
The PCB can also be integrated into an RMQ22 housing.
Do not connect any of the following points to an external potential:
O-, I+, I1, I2, I3, I4
The connections are electrically connected with the AS-i cable.
Install the unit so that exposed parts cannot be touched.
Pack quantity 1 pcs.