1. Homepage
  2. Products
  3. Industrial communication
  4. AS-Interface I/O modules
  5. Compact field modules with screw mounting CompactLine
  6. AC2489

AS-Interface CompactLine module

CompactM8 2 x 4 DI A/B

AC2489

{{'OPTIONAL_INFO' | productAvailability | error}}

Dear customer,
Unfortunately, this data sheet is not available in the requested language. If you have any further questions, you can contact us by e-mail.

Best regards
Your ifm team


Price does not include VAT

  • ce
  • asi
  • cul
Download
Technische Details
Electrical data
Operating voltage [V] 26.5...31.6 DC; ("supply class 2" to cULus)
Max. current consumption from AS-i [mA] 250
Inputs / outputs
Number of inputs and outputs Number of digital inputs: 8
Inputs
Number of digital inputs 8; (2 x Slave)
Input circuit of digital inputs PNP; (type 2 according to IEC 61131-2)
voltage supply [V] 18...30
Max. total current rating of inputs [mA] 180
Min. switching level high signal [V] 11
Digital inputs protected against short circuits yes
Sensor supply of the inputs AS-i
Outputs
Electrical design AS-i
Operating conditions
Ambient temperature [°C] -25...60
Max. relative air humidity [%] 90; (non condensing)
Max. height above sea level [m] 2000
Protection IP 65; IP 67; IP 68
Tests / approvals
EMC
EN 62026-2
EN 61000-6-2
EN 61000-6-3
AS-i classification
AS-i version 3.0
Extended addressing mode possible yes
AS-i profile S-0.A.E
AS-i I/O configuration [hex] 0
AS-i ID code [hex] A.E
AS-i certificate 133901
Assignment of the data bits
data bit D0 D1 D2 D3
input 1 2 3 4
socket I-1 I-2 I-3 I-4
pin 4 4 4 4
Assignment of the parameter bits
parameter bit Designation
P0 not used
P1 peripheral fault indication 1 activated
0 deactivated
P2 not used
P3 not used
Mechanical data
Weight [g] 153.4
Type of mounting backplane mounting
Materials PBT
Displays / operating elements
Display
switching status LED, yellow
operation LED, green
errors LED, red
Accessories
Accessories (supplied)
Label tags
Protective caps: 2
Accessories (optional)
Protective cap: M8, E73005
Flat cable insulation displacement connector, with 0.6 m round cable, E70483
Flat cable insulation displacement connector: M12, E70096
DIN rail adapter, E73007
Remarks
Remarks
Do not connect any of the following points to an external potential:
I-, I+, I1, I2, I3, I4
The connections are electrically connected with the AS-i cable.
default setting of the ID1 codes: slave 1=1 / slave 2=2
Pack quantity 1 pcs.
Electrical connection - Inputs
Connector: M8
Electrical connection - AS-i
Connector: M12