Control monitor for flow sensors
SN0001
VS0100 Typ VN31 Ex
Control monitor for flow sensors
SN0001
VS0100 Typ VN31 Ex
Article no longer available - archive entry
Application
Application | Flow monitoring |
---|
Electrical data
Operating voltage tolerance [%] | -10...10 |
---|---|
Operating voltage [V] | < 230 AC |
Max. power consumption [VA] | 2 |
Power-on delay time [s] | < 30 |
Outputs
Switching function flow monitoring | relay energised when flow is present |
---|
Software / programming
Adjustment of the switch point | potentiometer |
---|
Operating conditions
Ambient temperature [°C] | 0...60 |
---|---|
Protection | IP 40 |
Protection rating terminals | IP 20 |
Tests / approvals
Approval | PTB Ex-86/2141 |
---|
Safety classification
Designation | in protection rating intrinsic safety |
---|---|
Voltage [V] | 12,6 |
Current [mA] | 194 |
Power [mW] | 612 |
[Ex ia] IIC designation | [EEx] ib IIC |
[Ex ia] IIC inductance | 0.5 mH |
[Ex ia] IIC capacitance | 800 nF |
Mechanical data
Housing | housing for DIN rail mounting |
---|---|
Dimensions [mm] | 75 x 55 x 110 |
Materials | plastics |
Displays / operating elements
Display |
|
---|
Electrical connection
Relay circuit AC | ... 250 AV,...6 A cos j > 0,7 |
---|---|
Relay circuit DC | ...60 DC,...0,6 A, L/R < 200 ms /...24 DC, ...4 A, L/R < 200 ms |
Remarks
Pack quantity | 1 pcs. |
---|
Electrical connection
Connection | terminals: 16 x ...2.5 mm² |
---|