You probably do not come from: Israel. If necessary, change to: United States
  1. Products
  2. Industrial communication
  3. AS-Interface I/O modules
  4. Compact field modules with screw mounting CompactLine
  5. AC2490

AS-Interface CompactLine module

AC2490

CompactM8 4 DI 4 DO

AS-Interface CompactLine module

AC2490

CompactM8 4 DI 4 DO

  • ce
  • asi
  • cul
Application
Design only for operation with AS-i masters with the profile M4, for the connection of mechanical contacts a suitable sensor is to be connected to any input
Application field installation
Electrical data
Operating voltage [V] 26.5...31.6 DC
Max. current consumption from AS-i [mA] 230
Additional voltage supply [V] 15...30 DC; (AUX)
Max. current consumption from additional supply [mA] 1000; (AUX; < 40 °C: 2 A)
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital inputs: 4; Number of digital outputs: 4
Inputs
Number of digital inputs 4
Input circuit of digital inputs PNP; (type 2 according to IEC 61131-2)
Sensor supply of the inputs AS-i
Power supply [V] 18...30; (DC)
Max. total current rating of inputs [mA] 180
Input current High [mA] 6...10
Input current Low [mA] 0...2
Switching level high [V] > 11
Digital inputs protected against short circuits yes
Outputs
Number of digital outputs 4
Circuit PNP
Voltage range DC [V] 15...30; (AUX)
Max. current load per output [mA] 500; (< 40 °C: 1000 mA)
Short-circuit proof yes
Electrically separated yes
Actuator supply outputs AUX
Operating conditions
Ambient temperature [°C] -25...60
Storage temperature [°C] -25...60
Max. relative air humidity [%] 90; (non condensing)
Max. height above sea level [m] 2000
Protection IP 65; IP 67; IP 68
Tests / approvals
EMC
EN 62026-2
EN 50581
MTTF [years] 278
UL approval
power supply Class 2
AS-i classification
AS-i version 3.0
Extended addressing mode yes
AS-i master profile M4
AS-i profile S-7.A.7
AS-i I/O configuration [hex] 7
AS-i ID code [hex] A.7
Assignment of the data bits
data bit D0 D1 D2 D3
input 1 2 3 4
socket I-1 I-2 I-3 I-4
pin 4 4 4 4
Output 1 2 3 4
socket O-1 O-2 O-3 O-4
pin 4 4 4 4
Assignment of the parameter bits
parameter bit Designation
P0 not used
P1 peripheral fault indication : 1 activated / 0 deactivated
P2 not used
P3 not used
Mechanical data
Weight [g] 150
Type of mounting backplane mounting
Dimensions [mm] 134.5 x 30 x 23.5
Materials PBT
Displays / operating elements
Display
switching status LED, yellow I1...I4, O1...O4
operation LED, green AS-i, AUX
errors LED, red
Electrical connection
Module connection M12
Accessories
Items supplied
Label tags
Protective caps: 2
Accessories (optional)
Protective cap: M8, E73005
Flat cable insulation displacement connector: 1 m, round cable, E70582
DIN rail adapter:, E73007
Remarks
Remarks
Do not connect any of the following points to an external potential:
I-, I+, I1, I2, I3, I4
The connections are electrically connected with the AS-i cable.
Pack quantity 1 pcs.
Electrical connection - AS-i
Connector: 1 x M12; coding: A
Electrical connection - Inputs
Connector: 4 x M8; coding: A
Electrical connection - Outputs
Connector: 4 x M8; coding: A