Product characteristics | |||
---|---|---|---|
Output function | normally closed | ||
Sensing range [mm] | 4...20 | ||
Housing | threaded type | ||
Dimensions [mm] | M38 x 1.5 | ||
Electrical data | |||
Operating voltage [V] | 20...250 AC/DC | ||
Current consumption [mA] | < 2 | ||
Protection class | II | ||
Reverse polarity protection | no | ||
Outputs | |||
Output function | normally closed | ||
Max. voltage drop switching output DC [V] | 6 | ||
Max. voltage drop switching output AC [V] | 6 | ||
Minimum load current [mA] | 4 | ||
Permanent current rating of switching output AC [mA] | 250; (350 (...50 °C)) | ||
Permanent current rating of switching output DC [mA] | 100 | ||
Short-time current rating of switching output [mA] | 2200; (50ms / 0,5Hz) | ||
Switching frequency AC [Hz] | 25 | ||
Switching frequency DC [Hz] | 40 | ||
Short-circuit proof | no | ||
Overload protection | no | ||
Detection zone | |||
Sensing range [mm] | 4...20 | ||
Sensing range adjustable | yes | ||
Factory setting sensing range [mm] | 20 | ||
Real sensing range Sr [mm] | 20 ± 10 % | ||
Operating distance [mm] | 0...16.2 | ||
Accuracy / deviations | |||
Correction factor | glass: 0.4 / water: 1 / ceramics: 0.2 / PVC: 0.2 | ||
Hysteresis [% of Sr] | 1...15 | ||
Switch point drift [% of Sr] | -15...15 | ||
Operating conditions | |||
Ambient temperature [°C] | -25...80 | ||
Protection | IP 65 | ||
Tests / approvals | |||
EMC |
|
||
Mechanical data | |||
Housing | threaded type | ||
Mounting | non-flush mountable | ||
Dimensions [mm] | M38 x 1.5 | ||
Thread designation | M38 x 1.5 | ||
Materials | brass white bronze coated; PBT | ||
Displays / operating elements | |||
Display |
|
||
Electrical connection | |||
Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting | ||
Accessories | |||
Items supplied |
|
||
Remarks | |||
Remarks |
|
||
Pack quantity | 1 pcs. | ||
Electrical connection | |||
Connection | Cable: 2 m, PVC; 3 x 0.5 mm² | ||