KI000A

KIE2150NFBOA/3D

Capacitive sensor

KI000A

KIE2150NFBOA/3D

  • For applications in hazardous areas
  • With combined AC/DC output stage
  • Easy setting of the sensing range via potentiometer
  • Two-wire technology
  • Output function normally open / normally closed programmable
  • ce
  • ccc
  • ukca
  • ex
Product characteristics
Output function normally open / normally closed; (selectable)
Sensing range [mm] 15
Housing threaded type
Dimensions [mm] M30 x 1.5 / L = 150
Electrical data
Operating voltage [V] 30...250 AC / 20...250 DC
Protection class II
Reverse polarity protection yes
Measuring principle capacitive
Outputs
Output function normally open / normally closed; (selectable)
Max. voltage drop switching output DC [V] 8
Max. voltage drop switching output AC [V] 10
Minimum load current [mA] 5
Max. leakage current [mA] 2.5 (250 V AC) / 1.7 (110 V AC) / 1.5 (24 V DC)
Permanent current rating of switching output AC [mA] 100; (150 (...40 °C))
Permanent current rating of switching output DC [mA] 100; (150 (...40 °C))
Short-time current rating of switching output [mA] 1000; (20ms / 0,5Hz)
Switching frequency AC [Hz] 10
Switching frequency DC [Hz] 10
Notes on switching frequency [Hz]
only for resistive loads; 2 Hz for utilisation category AC-140
Short-circuit proof no
Overload protection no
Detection zone
Sensing range [mm] 15
Sensing range adjustable yes
Factory setting sensing range [mm] 15
Real sensing range Sr [mm] 15 ± 10 %
Accuracy / deviations
Correction factor glass: 0.4 / water: 1 / ceramics: 0.2 / PVC: 0.2
Hysteresis [% of Sr] 1...15
Switch point drift [% of Sr] -20...20
Operating conditions
Ambient temperature [°C] -20...60
Protection IP 65; IP 67
Tests / approvals
ATEX marking II 3D Ex tc IIIC T90°C Dc X
EMC
EN 61000-4-2 ESD kV / 8 kV AD
EN 61000-4-3 HF radiated 3 V/m
EN 61000-4-4 Burst 2 kV
EN 61000-4-5 Surge 1 kV line to line, Ri: 2 Ohm
EN 61000-4-6 HF conducted 3 V
EN 55011 class B
MTTF [years] 305
Mechanical data
Weight [g] 150
Housing threaded type
Mounting non-flush mountable
Dimensions [mm] M30 x 1.5 / L = 150
Thread designation M30 x 1.5
Materials PBT; PA
Displays / operating elements
Display
switching status 1 x LED, yellow
Electrical connection
Required protection miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting; Place the fuse outside the hazardous area.
Accessories
Items supplied
lock nuts: 2
Remarks
Remarks
Recommendation: Check the safe functioning of the unit after a short circuit.
Pack quantity 1 pcs.
Electrical connection
Connection terminals: 0.34...2.5 mm²; Cable sheath: Ø 5...9 mm; Cable gland: M20 X 1.5