Electrical design | AS-i |
---|---|
Sensing range [mm] | 15 |
Housing | rectangular |
Dimensions [mm] | 40 x 40 x 54 |
Operating voltage [V] | 26.5...31.6 DC |
---|---|
Current consumption [mA] | < 35 |
Protection class | III |
Reverse polarity protection | yes |
Electrical design | AS-i |
---|---|
Switching frequency DC [Hz] | 100 |
Sensing range [mm] | 15 |
---|---|
Operating distance [mm] | 0...12.1 |
Correction factor | steel: 1 / stainless steel: 0.7 / brass: 0.5 / aluminium: 0.5 / copper: 0.4 |
---|---|
Hysteresis [% of Sr] | 1...20 |
Switch point drift [% of Sr] | -10...10 |
Ambient temperature [°C] | -25...70 |
---|---|
Protection | IP 67 |
EMC |
|
||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
MTTF [years] | 958 |
AS-i version | 3.0 | |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Extended addressing mode | yes | |||||||||||||||
AS-i I/O configuration [hex] | 0 | |||||||||||||||
AS-i ID code [hex] | A.E | |||||||||||||||
AS-i certificate | 71901 | |||||||||||||||
Assignment of the data bits |
|
Weight [g] | 151.5 |
---|---|
Housing | rectangular |
Sensing face | 5 positions selectable |
Mounting | flush mountable |
Dimensions [mm] | 40 x 40 x 54 |
Materials | PBT; PPE |
Display |
|
---|
Pack quantity | 1 pcs. |
---|
Connection | Connector: 1 x M12; coding: A; Locking: locking, rotatable |
---|