  • For the reliable vibration monitoring of machines and equipment
  • Condition-based maintenance thanks to monitoring of unbalance, rolling element bearing or gear state
  • Inputs for the simultaneous detection of up to four vibration sensors
  • Two switching outputs for pre-alarm and main alarm
  • Analogue inputs for monitoring further measurement variables
  • ce
  • eac
  • cul
  • profinet
Download
Technische Details
Application
Design parameter setting via PC software VES004
Electrical data
Operating voltage tolerance [%] 20
Operating voltage [V] 24 DC
Current consumption [mA] 200; ((24 V DC))
Protection class III
Inputs / outputs
Total number of inputs and outputs 8; (configurable)
Number of inputs and outputs Number of analogue inputs: 2; Number of digital outputs: 2; Number of analogue outputs: 1
Inputs
Total number of inputs 6
Number of analogue inputs 2; (static)
Analogue input (current) [mA] 0...20
Resolution of analogue input 12
Dynamic input - signal 0...10 mA IEPE / 0...20 mA
Dynamic input - resolution [bit] 16
Dynamic input - frequency range [Hz] 0...12000
Dynamic input - sampling rate [kSamples] 100
Outputs
Total number of outputs 2
Electrical design PNP
Number of digital outputs 2; (configurable)
Output function normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V] 2
Permanent current rating of switching output DC [mA] 100
Number of analogue outputs 1; (configurable)
Analogue current output [mA] 0...22
Max. load [Ω] 500
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
Measuring/setting range
Frequency range [Hz] 0...12000
Interfaces
Communication interface Ethernet
Protocol PROFINET IO
Operating conditions
Ambient temperature [°C] 0...60
Storage temperature [°C] 0...60
Protection IP 20
Tests / approvals
EMC
EN 61000-4-2 ESD 4 kV contact discharge / 15 kV air discharge
EN 61000-4-3 10 V/m (80...2700 MHz)
EN 61000-4-4 Burst 4 kV capacitive coupling probe, earthed
EN 61000-4-6 10 V 0,15...80 MHz
EN 61000-6-4 industrial environments
EN 50178
MTTF [years] 91
UL approval
UL Approval no. L001
Mechanical data
Weight [g] 296.5
Housing plastic housing
Type of mounting rail; (TH35/EN60715)
Dimensions [mm] 114.2 x 50 x 105.3
Materials PA
Data memories
With real-time clock yes
Accessories
Accessories (optional)
cross-over Ethernet patch cable for the direct connection to the PC
Remarks
Pack quantity 1 pcs.
Electrical connection
Connection COMBICON:
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — VSE150-00 — 17.03.2017 —