1. Homepage
  2. Products
  3. Condition monitoring systems
  4. Signalling and display systems
  5. IO-Link - Displays
  6. E30391

IO-Link display

IO-Link DISPLAY 1,44"

E30391

{{'OPTIONAL_INFO' | productAvailability | error}}

Dear customer,
Unfortunately, this data sheet is not available in the requested language. If you have any further questions, you can contact us by e-mail.

Best regards
Your ifm team

  • With text displays and dialogue box for free text
  • Colour change for text and background
  • Flexible adaptation of the display, also during operation
  • Easy integration into each IO-Link structure
  • cul
  • iolink
Download
Technische Details
Electrical data
Operating voltage [V] 18...30 DC
Current consumption [mA] < 47
Min. insulation resistance [MΩ] 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Software / programming
Parameter setting options display, indication (figure, text, QR code)
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
IO-Link device ID 681 d / 00 02 A9 h
Profiles Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
SIO mode no
Required master port type A
Process data binary 6
Min. process cycle time [ms] 8.4
Operating conditions
Ambient temperature [°C] 0...60
Storage temperature [°C] -20...80
Protection IP 65; IP 67
Tests / approvals
EMC
DIN EN 61000-6-2
DIN EN 61000-6-4
Shock resistance
DIN EN 60068-2-27 20 g (11 ms)
Vibration resistance
DIN EN 60068-2-6 20 g (10...50 Hz)
MTTF [years] 5.63
Mechanical data
Weight [g] 174
Materials stainless steel (1.4404 / 316L); PC; PBT-GF30; PPS; FKM; PA 6.6-GF30
Displays / operating elements
Display
colour display 1,44 "
resolution pixels 128 x 128
2 x LED, yellow
Remarks
Pack quantity 1 pcs.
Electrical connection
Connector: 1 x M12; Contacts: gold-plated
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — E30391-01 — 29.03.2016 —