AS-Interface ClassicLine module with quick mounting technology

ClassicLine IO-Link 2 Ports

AC5225

{{'OPTIONAL_INFO' | productAvailability | error}}

Dear customer,
Unfortunately, this data sheet is not available in the requested language. If you have any further questions, you can contact us by e-mail.

Best regards
Your ifm team

  • Easy toolless installation and wiring thanks to quick mounting technology
  • Three freely selectable directions of the flat cable
  • Clearly visible powerful LEDs for displaying operation, switching status and error
  • High protection rating for the requirements of harsh industrial environments
  • Robust M12 connectors for connecting sensors and actuators
  • ce
  • eac
  • asib
  • cul
Download
Technische Details
Application
Application only for operation with AS-i masters with the profile M4
Electrical data
Operating voltage [V] 26.5...31.6 DC
Max. current consumption from AS-i [mA] 300
Reverse polarity protection yes
Additional voltage supply [V] 20...30 DC
Inputs
Digital inputs protected against short circuits yes
Sensor supply of the inputs AS-i
Interfaces
Communication interface IO-Link; AS-i
IO-Link Device
Min. process cycle time [ms] 2.3
IO-Link Master
Transmission type COM 1 / COM 2
IO-Link revision 1.0
Number of ports class A 2
Operating conditions
Ambient temperature [°C] -25...70
Protection IP 67
Tests / approvals
EMC
EN 50295
MTTF [years] 149
AS-i classification
AS-i version 3.0
AS-i addressing addressing socket
AS-i profile S-7.5.5
AS-i I/O configuration [hex] 7
AS-i ID code [hex] 5.5
AS-i certificate pending yes
Mechanical data
Weight [g] 183
Materials PA; piercing contacts: CuSn6 nickel-plated and tin-plated
Displays / operating elements
Display
operation PWR LED, green Voltage AS-i
errors LED, red
switching status LED, yellow DI/DO Port 1, Port 2
communication LED, green IO-Link Port 1, Port 2
disturbed communication LED, red Port 1, Port 2
Accessories
Accessories (supplied)
lower part
Accessories (optional)
Protective cap: M12, E73004
Remarks
Remarks
When the sensors and actuators are supplied from AS-i the load must not exceed a maximum of 200 mA.
There is an electrical connection between the sensor and AS-i.
operating voltage "supply class 2" according to cULus
Pack quantity 1 pcs.
Electrical connection
quick mounting technology for AS-i flat cable: ; three orientations possible
Connector: M12