- Products
- AL1000
IO-Link master with PROFINET interface
AL1000
IO-Link Master PL PN 8P IP67
IO-Link master with PROFINET interface
AL1000
IO-Link Master PL PN 8P IP67
- Reliable transmission of machine data, process parameters and diagnostic data to the controller
- With integrated fieldbus interface
- Large operating temperature range and high protection rating
- Robust housing for use in harsh industrial environments
- For connection of up to eight IO-Link devices
phase-out article
Alternative articles: AL1202 Product comparison: AL1000 / AL1202 When selecting an alternative article and accessories please note that technical data may differ!
Application
Application | I/O modules for field applications |
---|---|
Daisy-chain function | power supply; fieldbus interface |
Electrical data
Operating voltage [V] | 19...31.2 DC; (US) |
---|---|
Protection class | III |
Additional voltage supply [V] | 19...31.2 DC; (UA) |
Current rating per port [A] | 1.6 |
---|
Current rating per port [A] | 0.2 |
---|
Inputs / outputs
Total number of inputs and outputs | 12; (configurable) |
---|---|
Number of inputs and outputs | Number of digital inputs: 12; Number of digital outputs: 8 |
Inputs
Number of digital inputs | 12; (IO-Link Port Class A: 4 x 2; IO-Link Port Class B: 4 x 1) |
---|---|
Switching level high [V] | 15...30 |
Switching level low [V] | -3...5 |
Digital inputs protected against short circuits | yes |
Outputs
Number of digital outputs | 8; (IO-Link Port Class A: 4 x 1; IO-Link Port Class B: 4 x 1) |
---|---|
Max. current load per output [mA] | 200 |
Short-circuit proof | yes |
Actuator supply outputs | 24 V DC |
Interfaces
Communication interface | Ethernet; IO-Link |
---|
Protocol | PROFINET |
---|
Transmission type | COM1 (4,8 kBaud); COM2 (38,4 kBaud); COM3 (230,4 kBaud) |
---|---|
IO-Link revision | 1.1 |
Number of ports class A | 4 |
Number of ports class B | 4 |
Operating conditions
Ambient temperature [°C] | -25...60 |
---|---|
Storage temperature [°C] | -25...85 |
Max. relative air humidity [%] | 95 |
Protection | IP 65; IP 67 |
Tests / approvals
EMC |
|
||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Shock resistance |
|
||||||||||||
Vibration resistance |
|
Mechanical data
Weight [g] | 574 |
---|---|
Materials | housing: PA; socket: brass nickel-plated |
Sealing material | FKM |
Remarks
Remarks |
|
|
---|---|---|
Pack quantity | 1 pcs. |
Electrical connection - Ethernet
IN / OUT X21, X22 | Connector: M12; coding: D; Sealing: FKM |
---|
Electrical connection - Process connection
IO-Link Port Class A X01...X04 | Connector: M12; coding: A; Sealing: FKM |
---|
Electrical connection - power supply IN
X31 | Connector: M12; coding: T |
---|
Electrical connection - power supply OUT
X32 | Connector: M12; coding: T; Sealing: FKM |
---|