Product characteristics |
Electrical design |
PNP/NPN |
Output function |
normally open |
Sensing range [mm] |
10 |
Housing |
rectangular |
Dimensions [mm] |
26 x 26 x 26 |
Electrical data |
Operating voltage [V] |
10...55 DC |
Protection class |
II |
Reverse polarity protection |
yes |
Outputs |
Electrical design |
PNP/NPN |
Output function |
normally open |
Max. voltage drop switching output DC [V] |
4.5 |
Minimum load current [mA] |
4 |
Max. leakage current [mA] |
0.6 |
Permanent current rating of switching output DC [mA] |
100 |
Switching frequency DC [Hz] |
250 |
Short-circuit protection |
yes |
Type of short-circuit protection |
pulsed |
Overload protection |
yes |
Detection zone |
Sensing range [mm] |
10 |
Real sensing range Sr [mm] |
10 ± 10 % |
Operating distance [mm] |
0...8.1 |
Accuracy / deviations |
Correction factor |
steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminium: 0.3 / copper: 0.2 |
Hysteresis [% of Sr] |
1...15 |
Switch point drift [% of Sr] |
-10...10 |
Operating conditions |
Ambient temperature [°C] |
-25...70 |
Protection |
IP 67 |
Tests / approvals |
EMC |
EN 60947-5-2 |
|
EN 55011 |
class B |
|
Mechanical data |
Housing |
rectangular |
Mounting |
flush mountable |
Dimensions [mm] |
26 x 26 x 26 |
Materials |
PBT |
Displays / operating elements |
Display |
switching status |
1 x LED, yellow |
|
Remarks |
Pack quantity |
1 pcs. |
Electrical connection - plug |
Connection |
Cable: 0.15 m, PUR |
Connection |
Connector: 1 x M12 |