Product characteristics
Output function | normally open / normally closed; (selectable) |
---|---|
Sensing range [mm] | 15 |
Housing | rectangular |
Dimensions [mm] | 40 x 40 x 121 |
Electrical data
Operating voltage [V] | 20...250 AC/DC |
---|---|
Protection class | II |
Reverse polarity protection | no |
Outputs
Output function | normally open / normally closed; (selectable) |
---|---|
Max. voltage drop switching output DC [V] | 6 |
Max. voltage drop switching output AC [V] | 6.5 |
Minimum load current [mA] | 5 |
Max. leakage current [mA] | 2.5 (250 V AC) / 1.3 (130 V AC) / 0.8 (24 V DC) |
Permanent current rating of switching output AC [mA] | 150; (350 (...50 °C); when used outside the hazardous area: 250 (...80 °C)) |
Permanent current rating of switching output DC [mA] | 100; (350 (...50 °C); when used outside the hazardous area: 250 (...80 °C)) |
Short-time current rating of switching output [mA] | 2200; (20 ms / 0,5 Hz) |
Switching frequency AC [Hz] | 25 |
Switching frequency DC [Hz] | 70 |
Short-circuit proof | no |
Overload protection | no |
Detection zone
Sensing range [mm] | 15 |
---|---|
Real sensing range Sr [mm] | 15 ± 10 % |
Operating distance [mm] | 0...12.1 |
Accuracy / deviations
Correction factor | steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminium: 0.3 / copper: 0.2 |
---|---|
Hysteresis [% of Sr] | 1...15 |
Switch point drift [% of Sr] | -10...10 |
Operating conditions
Ambient temperature [°C] | -20...60 | |
---|---|---|
Note on ambient temperature |
|
|
Protection | IP 54; (when used outside the hazardous area: IP 65) |
Tests / approvals
ATEX marking | II 3D Ex tD A22 IP54 T95°C X | ||
---|---|---|---|
EMC |
|
Mechanical data
Weight [g] | 0.211 |
---|---|
Housing | rectangular |
Mounting | flush mountable |
Dimensions [mm] | 40 x 40 x 121 |
Materials | PPE |
Tightening torque for cable gland [Nm] | 3.5 |
Displays / operating elements
Display |
|
---|
Electrical connection
Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting; Place the fuse outside the hazardous area. |
---|
Remarks
Remarks |
|
||
---|---|---|---|
Pack quantity | 1 pcs. |
Electrical connection
Connection | terminals: ...2.5 mm²; Cable sheath: Ø 5.5...13 mm |
---|