Housing | housing for DIN rail mounting |
---|---|
Dimensions [mm] | 75 x 100 x 110 |
Application | evaluation of pulse sequences with regard to reaching a minimum rotational speed in plants; centrifuges; agitators |
---|
Nominal voltage AC [V] | < 230 |
---|---|
Nominal voltage DC [V] | 24 |
Nominal voltage tolerance [%] | 10 |
Nominal voltage tolerance 2 [%] | 10 |
Nominal frequency AC [Hz] | 50...60 |
Auxiliary energy for sensors DC [V] | 24 |
Number of inputs and outputs | Number of relay outputs: 3 |
---|
Number of relay outputs | 3 |
---|---|
Contact rating | 4 A / 250 V AC (30 V DC) |
Setting range [Imp/min] | 50...500 |
---|
Hysteresis [% of Sr] | < 5 |
---|---|
Repeatability [% of Sr] | < 5 |
Ambient temperature [°C] | 0...55 |
---|---|
Protection | IP 40 |
Protection rating terminals | IP 20 |
Housing | housing for DIN rail mounting |
---|---|
Dimensions [mm] | 75 x 100 x 110 |
Materials | plastics |
Display |
|
---|
Remarks |
|
---|
Connection | terminals: ...2.5 mm² |
---|