IO-Link master with EtherNet/IP interface

IO-Link Master CL EIP 8P IP20


Dear customer,
Unfortunately, this data sheet is not available in the requested language. If you have any further questions, you can contact us by e-mail.

Best regards
Your ifm team

  • Reliable transmission of machine data, process parameters and diagnostic data to the controller
  • For connection of up to eight IO-Link devices
  • Two Ethernet ports with integrated switch
  • Integrated web server for configuration and diagnostics
  • Simultaneous data exchange with the controller and the IT world
  • ce
  • cul
Comprehensive technical data in pdf format

Technische Details
Application I/O modules for use in the control cabinet
Electrical data
Operating voltage [V] 18...30 DC
Nominal voltage DC [V] 24
Max. power consumption [VA] 2.4
Max. current load total [A] 2
Inputs / outputs
Total number of inputs and outputs 20
Number of digital inputs 18; (8 x 2 + 2 x 1)
Input circuit of digital inputs PNP
voltage supply [V] 24
Max. total current rating of inputs [mA] 1600
Input current limitation [mA] 200
Short-circuit protection digital inputs yes
Digital inputs protected against short circuits yes
Overload protection digital inputs yes
Number of digital outputs 10
Beschaltung PNP
Max. current load per output [mA] 200
Short-circuit protection yes
Electrically separated no
Actuator supply switching outputs 24 V DC
Communication interface IO-Link
Transmission rate 10; 100
Protocol EtherNet/IP; Modbus TCP
IO-Link Master
Transmission type COM 1 / COM 2 / COM 3
IO-Link revision 1.1
SDCI standard IEC 61131-9
Number of ports class A 8
Operating conditions
Ambient temperature [°C] 0...70
Storage temperature [°C] -20...70
Max. relative air humidity [%] 95
Protection IP 20
Tests / approvals
Shock/vibration resistance EN60068-2-6; EN60068-2-27
Mechanical data
Weight [g] 405.2
Dimensions [mm] 105.3 x 45.2 x 113.6
Materials housing: PA
Displays / operating elements
switching status LED, yellow
operation LED, green
errors LED, red
function LED, yellow
Pack quantity 1 pcs.
Electrical connection
screw terminals: ; Maximum cable length: 20 m