1. Homepage
  2. Products
  3. Industrial communication
  4. AS-Interface I/O modules
  5. PCB solutions
  6. AC2704

Article no longer available - archive entry

Alternative article: AC2251 – Product comparison: AC2704 / AC2251
Note any deviating technical data for the selection of the alternative article and the accessories.
discontinued article
Date of discontinuation: {{"2016-03-31T00:00:00.000+02:00" | date}}

AC2704

AS-Interface control cabinet module

CabinetModule 4DI 4DO T ST

{{'OPTIONAL_INFO' | productAvailability | error}}

Dear customer,
Unfortunately, this data sheet is not available in the requested language. If you have any further questions, you can contact us by e-mail.

Best regards
Your ifm team

  • For use in control cabinets
  • Simple and fast wiring by means of cage clamps
  • Particularly space-saving design
  • Double terminals for looping through the voltage supply
  • Clearly visible powerful LEDs for displaying operation, status and function
  • ce
  • asib
  • cul
Download
Technische Details
Electrical data
Operating voltage [V] 26.5...31.6 DC
Current consumption [mA] < 280
Max. current load total [A] 4
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital inputs: 4; Number of digital outputs: 4
Inputs
Number of digital inputs 4
Input circuit of digital inputs PNP
Sensor supply of the inputs AS-i
Voltage supply [V] 18...30
Max. total current rating of inputs [mA] 200
Input current High [mA] > 5
Input current Low [mA] < 1.5
Min. switching level high signal [V] 10
Digital inputs protected against short circuits yes
Outputs
Number of digital outputs 4
Circuit PNP
Voltage range DC [V] 10...30; (to PELV)
Max. current load per output [mA] 1000
Short-circuit proof yes
Electrically separated yes
Operating conditions
Ambient temperature [°C] -25...70
Protection IP 20
Tests / approvals
EMC
EN 50295
MTTF [years] 188
AS-i classification
AS-i profile S-7.0
AS-i I/O configuration [hex] 7
AS-i ID code [hex] 0
AS-i certificate pending yes
Mechanical data
Weight [g] 134
Type of mounting mounting on DIN rail and panel; string mounting possible
Materials PA; PVC
Displays / operating elements
Display
switching status LED, yellow
operation LED, green
short circuit LED, red
Remarks
Remarks
Do not connect any of the following points to an external potential:
I-, I+, I1, I2, I3, I4
The connections are electrically connected with the AS-i cable.
Notes discontinued article
Pack quantity 1 pcs.
Electrical connection
Connection screw terminals:
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — AC2704-01 — 13.02.2006 —