Product characteristics |
Number of inputs and outputs |
Number of digital outputs: 2; Number of analogue outputs: 1 |
Measuring range [m³/h] |
15...4400 |
Process connection |
flange DN100 according to: DIN 2448 |
Application |
Application |
totaliser function |
Media |
compressed air |
Note on media |
air quality ISO 8573-1 |
class 141 |
class 344 |
|
Medium temperature [°C] |
0...60 |
Pressure rating [bar] |
16 |
Electrical data |
Operating voltage [V] |
19...30 DC |
Current consumption [mA] |
< 100 |
Protection class |
III |
Reverse polarity protection |
yes |
Power-on delay time [s] |
0.5 |
Inputs / outputs |
Number of inputs and outputs |
Number of digital outputs: 2; Number of analogue outputs: 1 |
Outputs |
Total number of outputs |
2 |
Output signal |
switching signal; analogue signal; pulse signal; (configurable) |
Electrical design |
PNP |
Number of digital outputs |
2 |
Output function |
normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] |
2 |
Permanent current rating of switching output DC [mA] |
250; (per output) |
Number of analogue outputs |
1 |
Analogue current output [mA] |
4...20; (scalable) |
Max. load [Ω] |
500 |
Pulse output |
consumed quantity meter |
Short-circuit protection |
yes |
Type of short-circuit protection |
pulsed |
Overload protection |
yes |
Measuring/setting range |
Measuring range [m³/h] |
15...4400 |
Display range [m³/h] |
0...5320 |
Volumetric flow quantity monitoring |
Pulse value |
10 Nm³ |
Pulse length [s] |
0,1 |
Accuracy / deviations |
Flow monitoring |
Accuracy (in the measuring range) |
± (3 % MW + 0,3 % MEW) / ± (6 % MW + 0,6 % MEW); (class 141 / ; class 344) |
Response times |
Flow monitoring |
Response time [s] |
0 |
Operating conditions |
Ambient temperature [°C] |
0...60 |
Storage temperature [°C] |
-20...85 |
Max. relative air humidity [%] |
90 |
Protection |
IP 65 |
Tests / approvals |
EMC |
EN 61000-4-2 ESD |
4 kV CD / 8 kV AD |
EN 61000-4-3 HF radiated |
10 V/m |
EN 61000-4-4 Burst |
2 kV |
EN 61000-4-6 HF conducted |
10 V |
|
Vibration resistance |
DIN IEC 68-2-6 |
5 g (55...2000 Hz) |
|
MTTF [years] |
214 |
Mechanical data |
Weight [g] |
13873 |
Materials |
PBT-GF20; PC; PC; stainless steel (1.4301 / 304); FKM; pipe section: steel galvanised |
Materials (wetted parts) |
stainless steel (1.4401 / 316); stainless steel (1.4301 / 304); ceramics glass passivated; PEEK; polyester; FKM; aluminium anodised; steel galvanised |
Process connection |
flange DN100 according to: DIN 2448 |
Remarks |
Remarks |
MW = measured value |
MEW = Final value of the measuring range |
Measuring, display and setting ranges refer to the standard volume flow according to DIN ISO 2533. |
For information about installation and operation please see the operating instructions. |
|
Pack quantity |
1 pcs. |
Electrical connection |
Connection |
Connector: 1 x M12 |