Electrical data |
Operating voltage [V] |
26.5...31.6 DC |
Current consumption [mA] |
< 280 |
Max. current load total [A] |
6 |
Inputs / outputs |
Number of inputs and outputs |
Number of digital inputs: 4; Number of relay outputs: 4 |
Inputs |
Number of digital inputs |
4 |
Input circuit of digital inputs |
PNP |
Sensor supply of the inputs |
AS-i |
Voltage supply [V] |
18...30 |
Max. total current rating of inputs [mA] |
200 |
Input current High [mA] |
> 3 |
Input current Low [mA] |
< 1.5 |
Min. switching level high signal [V] |
10 |
Digital inputs protected against short circuits |
yes |
Outputs |
Electrical design |
AS-i |
Voltage range DC [V] |
24 |
Voltage range AC [V] |
240 |
Max. current load per output [mA] |
2500 |
Number of relay outputs |
4 |
Electrically separated |
yes |
Operating conditions |
Ambient temperature [°C] |
-25...50 |
Protection |
IP 20 |
Tests / approvals |
EMC |
|
AS-i classification |
AS-i profile |
S-7.0 |
AS-i I/O configuration [hex] |
7 |
AS-i ID code [hex] |
0 |
AS-i certificate |
11601 |
Mechanical data |
Type of mounting |
mounting on DIN rail and panel; string mounting possible |
Dimensions [mm] |
45 x 135 x 51.5 |
Materials |
PA; PVC |
Displays / operating elements |
Display |
switching status |
LED, yellow |
operation |
LED, green |
|
Accessories |
Accessories (optional) |
COMBICON connectors, E70198 |
|
Remarks |
Remarks |
Do not connect any of the following points to an external potential: |
I-, I+, I1, I2, I3, I4 |
The connections are electrically connected with the AS-i cable. |
|
Pack quantity |
1 pcs. |
Electrical connection |
Connection |
COMBICON: |