1. Homepage
  2. Products
  3. AC1325

Article no longer available - archive entry

AC1325

AS-Interface PROFIBUS DP gateway

ASI DP GATEWAY 1 MASTER

{{'OPTIONAL_INFO' | productAvailability | error}}

Dear customer,
Unfortunately, this data sheet is not available in the requested language. If you have any further questions, you can contact us by e-mail.

Best regards
Your ifm team

  • ce
  • asi
  • cul

Download
Technische Details
Application
Application use as Profibus DP gateway with 1 AS-i master
Electrical data
Operating voltage [V] 24 DC; (operating voltage "supply class 2" according to cULus)
Insulation rating [V] 500
Current consumption [mA] < 400
Max. current consumption from AS-i [mA] 10
Max. power consumption [VA] 10
Number of AS-i masters 1
Electrical separation yes
Interfaces
Communication interface PROFIBUS
PROFIBUS
Transmission standard EN 50170
Transmission rate 12 MBaud
Protocol Profibus DP
Usage type data transmission
at_schnittstelle-zusatz diagnostic function
Operating conditions
Ambient temperature [°C] 0...60
Storage temperature [°C] -20...70
Max. relative air humidity [%] 95
Protection IP 20
AS-i classification
AS-i version 2.1
AS-i profile M3
AS-i certificate 61105
Mechanical data
Weight [g] 545.6
Housing housing for DIN rail mounting
Materials aluminium; steel sheet galvanised
Displays / operating elements
Display
function 2 x LED, red
2 x LED, green
1 x LED, yellow
full graphic LCD display
Remarks
Pack quantity 1 pcs.
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — AC1325-00 — 09.05.2008 —