- Products
- SR0125
Application
Application | Flow monitoring; Wire monitoring |
---|
Electrical data
Operating voltage tolerance [%] | -20...20 |
---|---|
Operating voltage [V] | 24 DC |
Current consumption [mA] | 70 |
Power-on delay time [s] | 30 |
Number of channels | 1 |
Outputs
Electrical design | relay |
---|---|
Contact rating | 4 A, 250 V AC |
Switching function flow monitoring | relay energised when flow is present |
Switching function wire break monitoring | relay de-energised in case of wire break |
Response times
Response time [s] | < 10 |
---|
Software / programming
Adjustment of the switch point | potentiometer |
---|---|
Selection liquids / gases | slide switch |
Operating conditions
Ambient temperature [°C] | -25...60 |
---|---|
Protection | IP 40 |
Protection rating terminals | IP 20 |
Mechanical data
Housing | housing for DIN rail mounting |
---|---|
Dimensions [mm] | 75 x 55 x 110 |
Materials | plastics |
Displays / operating elements
Display |
|
---|
Remarks
Pack quantity | 1 pcs. |
---|
Electrical connection
Connection | terminals: 16 x ...2.5 mm² |
---|